Key Options
8-6 Samsung Electronics
How to set the key function of the outdoor unit (cont.)
䒲 AM140/160/180/200/220/240/260/280/300KXV6666
AM080/100/120/140/160/180/200/220/240/260/280/300MXVA6C
Optional item Input unit SEG1 SEG2 SEG3 SEG4 Function of the option Remarks
Emergency
operation for
compressor
malfunction
Individual 00
0 0 Disabled (Factory default)
E560 will occur when all
the compressors are set as
malfunction state.
0 1
Set compressor 1 as
malfunction state
02
Set compressor 2 as
malfunction state
Cooling capacity
correction
Main 0 1
00 7~9
Targeted evaporation
temperature [°C]
(When low temperature
value is set, discharged air
temperature of the indoor unit
will decrease)
0 1 5~7(Factory default)
02 9~11
03 10~12
0 4 11~13
05 12~14
06 13~15
Capcity
correction for
heating
Main 0 2
00 3 0 (Factory default)
Targeted high pressure [MPa]
(When low pressure value
is set, discharged air
temperature of the indoor
unit will decrease)
0 1 2 5
02
2 6
03 2 7
0 4 2 8
05 2 9
06 3 1
07 3 2
0 8 3 3
Current
restriction rate
Individual 03
00 100% (Factory default)
When restriction option is
set, cooling and heating
performance may decrease.
0 195 %
02 90 %
03 85 %
0 480 %
05
75 %
06 70 %
07 65 %
0 8 60 %
0 9 55 %
1 050 %
11 No restriction
Oil collection
interval
Main 0 4
0 0 Factory default
0 1 Shorten the interval by 1/2
Temperature to
trigger defrost
operation
Main 0 5
0 0 Factory default
0 1
Apply setting when the
product is being installed in
humid area such as near river
or lake
Fan speed
correction for
outdoor unit
Individual 06
0 0 Factory default
0 1 Increase fan speed
Increase the outdoor unit's fan
speed to maximum value.
Silent mode for
night-time
Main 0 7
0 0 Disabled (Factory default)Enables the silent mode
for night-time (It operates
automatically depending on
the temperature )
However, if the external
contact interface module
(MIM-B14) is used, entering
the silent mode is available
with contact signal
0 1LEVEL 1 / Auto
02 LEVEL 2 / Auto
03 LEVEL 3 / Auto
0 4LEVEL 1 / External contact
05 LEVEL 2 / External contact
06 LEVEL 3 / External contact
High-head
condition setting
Main 0 8
0 0 Disabled (Factory default)
0 1
Level 1 of height difference
type 1 (Indoor unit is lower
than outdoor unit)
When outdoor unit is located
40~80m above the indoor
unit
02
Level 2 of height difference
type 1 (Indoor unit is lower
than outdoor unit)
When outdoor unit is located
over 80m above the indoor
unit
03
Height difference type 2
(Outdoor unit is lower than
indoor unit)
When indoor unit is over 30 m
above the outdoor unit