Troubleshooting
4-16 Samsung Electronics
غ Initial Tracking (Communication Check-up) - Display for Problem
1
. For the display module of the outdoor unit, there are dierences in the contents displayed depending on whether the relevant outdoor
unit is a master unit or a sub unit.
1) Master Unit
م
The outdoor unit Micom attempts communication with the indoor unit connected to the communication cable (F1/F2) when the power is turned on.
م
Basic segment display
Step Display content Display
At initial power input
Checking segment
display
SEG1 SEG2 SEG3 SEG4
"8" "8" "8" "8"
While setting
communication
between indoor and
outdoor unit
(Addressing)
Number of
connected indoor
units
SEG1 SEG2 SEG3, 4 SEG3, 4
"A" " d"
Number of communicated units
ఐRefer to "View Mode" for
communication address
After communication
setting
(usual occasion)
Transmit/
Reception address
SEG1 SEG2 SEG3, 4 SEG3, 4
I/U : “A”
MCU : “C”
I/U : “0”
MCU : “1”
Reception address
(in decimal number)
ఐ I/U : Indoor unit
م
If the number of indoor units set by the outdoor unit is not in accordance with the number of indoor units that succeeded with
communication, then the four displaying parts will display
.
2) Sub(Slave) Unit
م
The two left hand displays show its own address and the two right hand displays show the outdoor unit's address.
Main address : C8, Sub1 address : C9, Sub2 address : CA, Sub3 address : CB
2
. The number of the indoor Units Connected to the outdoor unit can be congured by using the indoor unit installation quantity setup switch.
g
SEG1
af
G1
G2
bc e d
SEG2
g
SEG3
af
G1
G2
bc e d
SEG4
Outdoor Unit Display Parts
3. If the quantity of the indoor units congured with the indoor unit installation quantity setup switch does not match the quantity of
the indoor units found during the tracking process, E201 and U200 will be displayed in order on the display module.
4. When you install more than one MCU, set the quantity of installed MCU.
غ
Indoor Unit Installation Quantity Setup Switch
The following is an example of how to use the switch according to the num-
ber of indoor unit installations. The maximum number of possible indoor unit
connections is 64.
10’s Digit
(0~9)
1’s Digit
(0~9)
3Units Connected 17Units Connected 31Units Connected 64Units Connected
10’s Digit
0
1’s Digit
3
10’s Digit
1
1’s Digit
7
10’s Digit
3
1’s Digit
1
10’s Digit
6
1’s Digit
4
Indoor Unit
Installed
Quantity
MCU
Installed
Quantity