EasyManua.ls Logo

Samsung AM080 XV Series - Page 28

Samsung AM080 XV Series
277 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Product Specications
Samsung Electronics 2-21
TYPE
DVM S
Model AM240HXVAGH AM260HXVAGH
Mode HP HP
Power Φ, V, Hz 3/AC380~415/50
Capacity
Horse Power HP 24 26
Cooling
kW 67.2 72.8
btu/h - -
Heating
kW 75.6 81.9
btu/h - -
Power
Power input
(Nominal)
Cooling 1)
kW
17.10 19.30
Heating 2) 19.80 21.80
Current Input
(Nominal)
Cooling 1)
A
26.83 30.28
Heating 2) 31.06 34.20
Running
Current"
Cooling A 26.83 30.28
Heating A 31.06 34.20
Max A 55 58
Power
Consumption
Cooling kW 26.83 30.28
Heating kW 31.06 34.20
MCA/MFA A 60.5/75 63.8/75
COP Nominal Cooling - 3.930 3.772
Nominal Heating - 3.818 3.757
ESEER (HP) - - -
Compressor Model - DS-GB066FA* DS-GB070FA*
Type INV x 2EA INV x 2EA
Output kW - -
Lubricant
Type - FVC68D FVC68D
Charging cc 6,200 6,200
Refrigerant Type - R410A R410A
Factory Charging kg 14.3 14.3
Fan Type - Propeller + BLDC Propeller + BLDC
Motor Output W 620 x 2 620 x 2
Airflow rate
/min
310 310
Piping
Connections
Liquid pipe
Φ, mm 15.88 19.05
Φ, inch 5/8" 3/4"
Gas pipe
Φ, mm 34.92 34.92
Φ, inch 1 3/8" 1 3/8"
High pressure gas pipe
Φ, mm - -
Φ, inch
Installation Limi-
tation
Max. Length m 200(220) 200(220)
Max. Height m 110.0(40.0) 110.0(40.0)
Cable Main Power(Below 20m) mm2 16 16
Communication mm2 VCTF 0.75 ~ 1.5(2P) VCTF 0.75 ~ 1.5(2P)
Set
Dimension
Net weight kg 360 360
Gross weight kg 370 370
Net dimension (WxHxD) mm 1,295 x 1,695 x 765 1,295 x 1,695 x 765
Gross dimension (WxHxD) mm 1,363 x 1,887 x 832 1,363 x 1,887 x 832
Operating Temp.
Range
Cooling
-5.0 ~ 48.0 -5.0 ~ 48.0
Heating
-25.0 ~ 24.0 -25.0 ~ 24.0
Outdoor Unit (cont.)
1. Proper form capacity standard of air conditioning
- Cooling capacity : It is figures that appear in indoor 27˚C DB/19°C WB, outdoor 35˚C DB, length 7.5m of piping, fall 0m standard.
- Heating capacity : It is figures that appear in indoor 20˚C DB, outdoor 7˚C DB, length 7.5m of piping, fall 0m standard.
2. If proper form heating capacity is outdoor temperature 7˚C standard and outdoor temperature goes down by below zero, heating capacity can drop according to temperature condition.
3. Need special load calculation in case of use by main heating in the winter, and please buy product for low temperature that heating effect excels at low temperature.
4. Maximum length between outdoor and indoor units allows up to 200m (Equivalent length 220m).
5. If the indoor unit is below, height length allows up to 110m (If over 50m, decide whether to install the PDM kit). If the outdoor unit is below, allowable height length is 40m.

Table of Contents