Product Specications
Samsung Electronics 2-59
Outdoor Unit (cont.)
Type
DVM S
Model
AM100JXVAGH/ET AM120JXVAGH/ET
Power Supply (Outdoor Unit) [Φ, #, V, Hz]
3,4,380-415,50 3,4,380-415,50
System Mode
HEAT PUMP HEAT PUMP
Performance (nominal)
10.00 HP 12.00 HP
Capacity
Cooling [kW]
28.00 kW 33.60 kW
Cooling [Btu/h]
95,500 Btu/h 114,600 Btu/h
Heating [kW]
28.00 kW 33.60 kW
Heating [Btu/h]
95,500 Btu/h 114,600 Btu/h
Power Input
(Rated)
Cooling 1)
6.85 kW 8.16 kW
Heating 2)
5.91 kW 7.13 kW
Current Input
(Rated)
Cooling 1)
11.00 A 13.10 A
Heating 2)
9.50 A 11.40 A
Power
MCA [A]
21.1 A 25.00 A
MFA [A]
32.0 A 32.00 A
Energy Eciency
EER (Rated Cooling)
4.09 4.12
COP (Rated Heating)
4.74 4.71
Compressor
Type
SSC Scroll x 1 SSC Scroll x 1
Output(kW)
(6.39) kW (6.39) kW
Model
DS-GB066FAVB x 1 DS-GB066FAVB x 1
Oil (Type)
PVE PVE
Oil (Initial Charge) [cc]
1100 cc 1100 cc
Fan
Type
Propeller Propeller
Motor (Output) [W]
830.0 x 1 W 830.0 x 1 W
Air Flow Rate (High / Mid / Low) [CMM]
170 CMM 220 CMM
Air Flow Rate(High/Mid/Low)[L/S]
2,833.33 3,666.67
External Static Pressure (Min / Std / Max) [mmAq]
8.00 mmAq 8.00 mmAq
External Static Pressure (Min / Std / Max) [Pa]
78.45 Pa 78.45 Pa
Piping
Connections
Liquid Pipe (Φ, mm)
9.52 mm 12.70 mm
Liquid Pipe (Φ, inch)
3/8" 1/2"
Gas Pipe (Φ, mm)
22.22 mm 28.58 mm
Gas Pipe (Φ, inch)
7/8" 1 1/8"
Discharge Gas Pipe (Φ, mm)
#NAME? #NAME?
Discharge Gas Pipe (Φ, inch)
- -
Oil Equalizing Pipe (Φ, mm)
#NAME? #NAME?
Oil Equalizing Pipe (Φ, inch)
- -
Installation Max. Length [m]
200 m 200 m
Installation Max. Height [m]
110 m 110 m
Field Wiring
Power Source Wire
- -
Transmission Cable
0.75 ~ 1.5 0.75 ~ 1.5
Refrigerant
Type
R410A(Fluorinated green-
house gas, GWP=2,088)
11.48tCO2e
R410A(Fluorinated green-
house gas, GWP=2,088)
13.57tCO2e
Factory Charging (kg)
5.50 kg 6.50 kg
Sound
Sound Pressure
58.0 dBA 62.0 dBA
Sound Power
79.0 dBA 81.0 dBA
External
Dimension
(Outdoor Unit)
Net Weight(kg)
197.0 kg 210.0 kg
Shipping Weight (kg)
204.0 kg 217 kg
Net Dimensions (WxHxD) (mm)
880 x 1,695 x 765 mm 880 x 1,695 x 765 mm
Shipping Dimensions (WxHxD) (mm)
948 x 1,887 x 832 mm 948 x 1,887 x 832 mm
Operating Temp.
Range
Cooling (℃)
-5.0 ~ 48.0 ℃ -5.0 ~ 48.0 ℃
Heating (℃)
-25.0 ~ 24.0 ℃ -25.0 ~ 24.0 ℃
1. Proper form capacity standard of air conditioning
- Cooling capacity : It is figures that appear in indoor 27˚C DB/19°C WB, outdoor 35˚C DB, length 7.5m of piping, fall 0m standard.
- Heating capacity : It is figures that appear in indoor 20˚C DB, outdoor 7˚C DB, length 7.5m of piping, fall 0m standard.
2. If proper form heating capacity is outdoor temperature 7˚C standard and outdoor temperature goes down by below zero, heating capacity can drop according to temperature condition.
3. Need special load calculation in case of use by main heating in the winter, and please buy product for low temperature that heating effect excels at low temperature.
4. Maximum length between outdoor and indoor units allows up to 200m (Equivalent length 220m).
5. If the indoor unit is below, height length allows up to 110m (If over 50m, decide whether to install the PDM kit). If the outdoor unit is below, allowable height length is 40m.