Product Specications
Samsung Electronics 2-63
Outdoor Unit (cont.)
Type
SUPER DVM HR
Model
AM240MXVGNR/ET AM260MXVGNR/ET
Mode
Cooling Only Cooling Only
Power Supply (Outdoor Unit) [Φ, #, V, Hz]
3,4,380-415,50/60 3,4,380-415,50/60
System Mode
HEAT RECOVERY HEAT RECOVERY
Performance (nominal)
24 HP 26 HP
Capacity
Cooling [kW]
67.2 kW 72.8 kW
Cooling [Btu/h]
229,300 Btu/h 248,400 Btu/h
Heating [kW]
67.2 kW 72.8 kW
Heating [Btu/h]
229,300 Btu/h 248,400 Btu/h
Power Input
(Rated)
Cooling 1)
18.61 kW 20.92 kW
Heating 2)
13.20 kW 15.17 kW
Current Input
(Rated)
Cooling 1)
29.80 A 33.60 A
Heating 2)
21.20 A 24.30 A
Power
MCA [A]
55.0 A 60.0 A
MFA [A]
63.0 A 75.0 A
Energy Eciency
EER (Rated Cooling)
3.61 3.48
COP (Rated Heating)
5.09 4.80
Compressor
Type
Scroll Inverter Scroll Inverter
Output(kW)
6.76 x 2 kW 7.81 x 2 kW
Model
DS-GB070FAVA x 2 DS4GJ5080FVA x 2
Oil (Type)
PVE PVE
Oil (Initial Charge) [cc]
1100 x 2 cc 1400 x 2 cc
Fan
Type
Propeller Propeller
Motor (Output) [W]
620 x 2 W 620 x 2 W
Air Flow Rate (High / Mid / Low) [CMM]
340 CMM 340 CMM
Air Flow Rate(High/Mid/Low)[L/S]
- -
External Static Pressure (Min / Std / Max)
[mmAq]
8.0 mmAq 8.0 mmAq
External Static Pressure (Min / Std / Max) [Pa]
- Pa - Pa
Piping Connec-
tions
Liquid Pipe (Φ, mm)
15.88 mm 19.05 mm
Liquid Pipe (Φ, inch)
5/8" 3/4"
Gas Pipe (Φ, mm)
34.92 mm 34.92 mm
Gas Pipe (Φ, inch)
1+3/8" 1+3/8"
Discharge Gas Pipe (Φ, mm)
28.58 mm 28.58 mm
Discharge Gas Pipe (Φ, inch)
1+1/8" 1+1/8"
Installation Max. Length [m]
200(220) m 200(220) m
Installation Max. Height [m]
50(110)/40(110) m 50(110)/40(110) m
Field Wiring
Power Source Wire
- -
Transmission Cable
0.75~1.5 0.75~1.5
Refrigerant
Type
R410A
(Fluorinated greenhouse gas,
GWP=2,088)
R410A
(Fluorinated greenhouse gas,
GWP=2,088)
Factory Charging (kg)
14.0 kg 14.0 kg
Factory Charging (tCO2e)
29.23 tCO2e 29.23 tCO2e
Sound
Sound Pressure
69 dBA 69 dBA
Sound Power
90 dBA 90 dBA
External Dimen-
sion
(Outdoor Unit)
Net Weight(kg)
350.0 kg 358.0 kg
Shipping Weight (kg)
372.0 kg 380.0 kg
Net Dimensions (WxHxD) (mm)
1295x1795x765 mm 1295x1795x765 mm
Shipping Dimensions (WxHxD) (mm)
1363x1987x832 mm 1363x1987x832 mm
Operating Temp.
Range
Cooling ()
-5 ~ 48 -5 ~ 48
Heating ()
-25 ~ 24 -25 ~ 24
1. Proper form capacity standard of air conditioning
- Cooling capacity : It is figures that appear in indoor 27˚C DB/19°C WB, outdoor 35˚C DB, length 7.5m of piping, fall 0m standard.
- Heating capacity : It is figures that appear in indoor 20˚C DB, outdoor 7˚C DB, length 7.5m of piping, fall 0m standard.
2. If proper form heating capacity is outdoor temperature 7˚C standard and outdoor temperature goes down by below zero, heating capacity can drop according to temperature condition.
3. Need special load calculation in case of use by main heating in the winter, and please buy product for low temperature that heating effect excels at low temperature.
4. Maximum length between outdoor and indoor units allows up to 200m (Equivalent length 220m).
5. If the indoor unit is below, height length allows up to 110m (If over 50m, decide whether to install the PDM kit). If the outdoor unit is below, allowable height length is 40m.

Table of Contents