Troubleshooting
Samsung Electronics 4-69
1.
Cause of problem
4-3-52 Option setting error of outdoor unit
(Operation) ×(Reservation) (Blast) ×(Filter) ×(Defrost)
• Option setting error of outdoor unit
(E2P option use of other model or set of the relevant outdoor unit, compressor breakdown)
• Refer to the judgment method below.
Indoor Unit Display
Judgment Method
Special Cause
Outdoor Unit Display
Download relevant model EEPROM and then reset.
Execute automatic commissioning for UP
cancellation after EEPROM download.
Set the compressor breakdown setting value as "not set"
When setting breakdown for repair and replace of
compressor : Change the setting after replace.
No
Yes
Is the Compressor breakdown
setting value is "not set"?
Connect outdoor unit EEPROM and then reset.
No
Yes
Is the outdoor unit EEPROM accurately connected to
connector?