Troubleshooting
Samsung Electronics 4-17
4-3-8 Setup Error for MCU Branch part – Setup Error for MCU Quantity Used
Judgment Method
• Occurs when the quantity of MCU is incorrectly set by the outdoor unit.
• Occurs when same addresses are found when two or more MCU are connected.
Outdoor Unit Display
Indoor Unit Display
Special Cause • Outdoor unit MCU setup and same address errors when connecting two or more MCUs .
1. Inspection Method : Check the Main PCB MCU quantity setting switch of the outdoor unit and check the installed MCU quantity
matches.
Check whether each MCU PCB address switch was duplicated.
To use, reset by pressing the K3 button of the outdoor unit after the reset is completed, or reset after turning off
the power and then turn it on again.
Example of MCU quantity setting error
ex) PCB MCU setting quantity of outdoor unit = 2 / MCU installed Quantity = 3
• Example of MCU address setting error
ex) Two among three of MCU address was set to 0
Outdoor Unit PCB
Quantity of
Indoor Unit
Quantity of
MCU
Indoor Unit: - MCU: 2
Address: 0
Address: 1
Address: 2
Outdoor Unit PCB
Quantity of
Indoor Unit
Quantity of
MCU
Indoor Unit: - MCU: 3
Duct, Cassette (1/2 Way),Console, Celing Cassette (4/Mini4 Way) Wall-mounted (NeoForte)
Operation
Defrost Timer Fan Filter/MPI
Operation
Defrost Timer Filter
Operation
Timer Turbo
24 27
× ×
×
× × × × ×
: ON ◑ : Flash × : OFF
Branch
Branch
Branch