Troubleshooting
Samsung Electronics 4-29
4-3-19 : Suction Temperature sensor breakaway error
Indoorunit display
Judgment Method
Cause of problem
∙ Judgment Method : Difference of suction temperature of compressor starting verge and suction temperature that is on present
operation : If less than 2 ℃ for 30 minutes to keep.(Judgment at heating operation only)
∙ Suction temperature sensor breakaway/defective.
Outdoor unit display
1.
Cause of problem
Complete
Is Suction sensor
and sensor Holder accurately
attached?
Is Suction sensor
resistance value reasonable?
(Refer to E231 )
Defective Sensor : Replace Sensor
No
Re-insert the sensor.
Re-attach the sensor holder.
No
Yes
Yes