EasyManua.ls Logo

Samsung AM080BXMDGH/EU - 4-3-14 Outdoor Temperature Sensor Error

Samsung AM080BXMDGH/EU
137 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting
Samsung Electronics 4-23
4-3-14 Outdoor Temperature Sensor Error
∙ Outdoor temperature sensor Open/Short is defective.
∙ Refer to the judgment method below.
Indoorunit display
Judgment Method
Cause of problem
Outdoor unit display
1.
Cause of problem
Did the outside temperature
sensor connector break away
from the PCB?
Did the resistance
value significantly stray from the following
temperature table?
After separating the outdoor temperature sensor
connector from the PCB, measure the resistance value
between the terminals.
Restart operation after replace the PCB
Restart operation after connecting
the connector to the PCB.
Replace this since it is the defective of
the outdoor temperature sensor itself.
Yes
No
No
Yes
Temperature (°C)
70
60
50
40
30
20
10
0
-10
Resistance (KΩ)
2.2
3.0
4.2
5.8
8.3
12.1
18.0
27.3
43.0
Resistance value measure part
OUT
OUT
Duct, Cassette (1/2 Way),Console, Celing Cassette (4/Mini4 Way) Wall-mounted (NeoForte)
Operation
Defrost Timer Fan Filter/MPI
Operation
Defrost Timer Filter
Operation
Timer Turbo
24 27
× ×
×
×
× × × ×
: ON ◑ : Flash × : OFF

Table of Contents