EasyManua.ls Logo

Samsung AM080BXMDGH/EU - 4-3-26 Suction-2 Temperature Sensor Error (OPEN;SHORT)

Samsung AM080BXMDGH/EU
137 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting
4-36 Samsung Electronics
4-3-26 Suction-2 Temperature Sensor Error (OPEN/SHORT)
• Disconnection or breakdown of relevant sensor
• Refer to the judgment method below.
Indoor Unit Display
Judgment Method
Special Cause
Outdoor Unit Display
1. Inspection Method
Yes
Did the connector for the
Suction-2 sensor break away from the PCB?
Did the resistance value
significantly stray from the following
temperature table?
Separate the connector of the Suction-2 sensor
from the PCB, and measure the resistance value
between the two terminals.
Restart operation after changing PCB
Restart operation after connecting the
connector to PCB
Change this part as it is the fault of the
outdoor Suction-2 sensor itself.
Yes
No
No
Temperature (°C)
70
60
50
40
30
20
10
0
-10
Resistance (KΩ)
2.2
3.0
4.2
5.8
8.3
12.1
18.0
27.3
43.0
Resistance value measure part
SUCT2
Duct, Cassette (1/2 Way),Console, Celing Cassette (4/Mini4 Way) Wall-mounted (NeoForte)
Operation
Defrost Timer Fan Filter/MPI
Operation
Defrost Timer Filter
Operation
Timer Turbo
24 27
× × × × × × × ×
: ON ◑ : Flash × : OFF

Table of Contents