Troubleshooting
4-14 Samsung Electronics
4-3-5 MCU branch part setup error – inconsecutive connection with the use of 2 branch parts
• Branch part assembly error
Criteria
Cause of problem
• When 2 branch parts are used for one indoor unit without connecting them consecutively.
Outdoor unit display
Indoor unit display
1. How to check
Find an MCU that is composed as the following picture to carry out assembly of branch part again. After completing the re-setting,
press K3 button on the button to reset or turn it off to restart.
MCU BOX #0
MCU PCB
OFF
MCU
address setup
ON
Setting error
Indoor unit
Indoor unit address
Branch part use setup
4 2 1 2 5 6
0
Branch A
4
B
2
C
D E
5
F
6
MCU BOX #0
MCU PCB
OFF
MCU
address setup
ON
Setting error
Indoor unit
Indoor unit address
Branch part use setup
4 2 2 2 5 6
0
Branch A
4
B
2
C
D E
5
F
6
Duct, Cassette (1/2 Way),Console, Celing Cassette (4/Mini4 Way) Wall-mounted (NeoForte)
Operation
Defrost Timer Fan Filter/MPI
Operation
Defrost Timer Filter
Operation
Timer Turbo
24℃ 27℃
× × ◑ ◑
×
× ◑ ◑ × × × ◑ ◑ ×
※ ● : ON ◑ : Flash × : OFF