Troubleshooting
4-40 Samsung Electronics
4-3-29 : Comp. Down due to Low Pressure Protection Control
Indoorunit display
Cause of problem
∙ Refrigerant shortage
∙ Electronic expansion valve blocked
∙ Service valve blocked
∙ Low pressure sensor defective
∙ Leakage of compressor discharge check valve of not-go-end outdoor unit
∙ Error may be found when used in temperature range outside the conditions of use
(Operating outside temperature at -20°C or less for heating and operating outside temperature at -5°C or less for Cooling)
Judgment Method
Judgment Method : Inspection when the value of low pressure sensor is 1.8kg//cm², or less for air conditioning and 0.8kg//cm² for heating
Outdoor unit display
1.
Cause of problem
Is the S-net
estimated value and the Manifold Gauge
value in range?
Are the Indoor Unit and Outdoor
Unit EEV normally operating?
Are there any blockage inside
the pipe? (filter etc.)
Check the refrigerant amount.
Is there any leakage in
the Liquid Pipe Valve or the discharge
check valve of the not-go-end Outdoor Unit when
only some Outdoor Units
are operating?
Auto Trial Operation
Open the Service Valve
Replace Low Pressure sensor
Check the relevant EEV
Pipe inspection
Replace relevant component
Yes
Yes
Yes
No
Are all service valves open?
Connect S-net and Manifold Gauge.
(essential requirement)
No
No
No
Yes
Yes
No
Duct, Cassette (1/2 Way),Console, Celing Cassette (4/Mini4 Way) Wall-mounted (NeoForte)
Operation
Defrost Timer Fan Filter/MPI
Operation
Defrost Timer Filter
Operation
Timer Turbo
24 27
× × × × ×
: ON ◑ : Flash × : OFF
(AMSSSFXVSSS)