Troubleshooting
Samsung Electronics 4-3
K3(Number of press) KEY operation Display on segment
1 time Intialize (Reset) setting Same as initial state
K4 (Press and hold to enter the setting)
K4 press (Number of press)
Displayed content
Display on segment
Page 1 Page 2
0 time Main version MAIN Ver. (ex) 1412)
1 time Inverter version INV1 Ver. (ex) 1412)
2 times EEP version EEP Ver. (ex) 1412)
3 times Assigned address of the units AUTO
SEG 1,2 SEG 3,4
Indoor unit:
A" , "0" Address (ex) 07)
4 times Manually assigned address of the units MANU
SEG 1,2 SEG 3,4
Indoor unit:
A" , "0" Address (ex) 15)
Even when the outdoor unit power is o , it is dangerous when you come in contact with inverter PCB since it is charged with high DC voltage.
When replacing/repairing the PCB, cut-o the power and wait until the DC voltage is discharged before replacing/repairing them. (Wait for more than 15
minutes to allow it to discharge naturally.)
When there were error, 'Dicharge mode of DC link voltage' may not have been e ective. Especialy if error E464 has been occured, power element might be
damaged by
re and therefore, do not use the 'Discharge mode of DC link voltage'.
During "Discharge mode of DC link voltage", voltage of INV will be displayed.
K4(Number of press) KEY operation
Display on segment
SEG 1 SEG2, 3, 4
1 time Outdoor unit model 1
AM080FXM
0, 0, 8
2 times Order frequency of compressor 2
120 Hz
1,2,0
3 times High pressure 3
1.52 MPa
1, 5, 2
4 times Low pressure 4
0.43 MPa
0, 4, 3
5 times Discharge temperature of compressor 5
87
°C
0, 8, 7
6 times IPM temperature of compressor 6
87
°C
0, 8, 7
7 times CT sensor value of compressor 7
2 A
0, 2, 0
8 t
imes Suction temperature 8
-42
°C
-, 4, 2
9 times COND OUT temperature 9
-42
°C
-, 4, 2
10 times Liquid pipe temperature A
-42
°C
-, 4, 2
11 times TOP temperature of compressor B
87
°C
0, 8, 7
12 times Outdoor temperature C
-42
°C
-, 4, 2
13 times
EVI inlet temperature
D
-42
°C
-, 4, 2
14 times
EVI outlet temperature
E
-42
°C
-, 4, 2
15 times
Main EEV step
F
2000 steps
2, 0, 0
16 times EVI EEV step G
300 steps
3, 0, 0
17 times
Fan step
H
13 steps
0, 1, 3
18 times
Current frequency of compressor
I
120 Hz
1,2,0
19 times
Master indoor unit address
J
Master indoor unit not seleted
BLANK , N , D
If indoor unit No.1 is seleted as the master unit
0 , 0 , 1