40_ installing the unit
installing the unit
INSULATING THE REFRIGERANT PIPE
Insulating the branch joint
Header joint
Fasten the header joint using a cable tie and cover the connected part.
Insulate the header joint and the welding part and wrap the connected part with an
adhesive insulation tape to prevent it from defrosting.
Outdoor joint & gas side of the outdoor unit
Use an insulation that should be able to handle the interior temperature over 120°C(248°F).
Wrap the branch joint with an insulation of a thickness of at least 10mm(3/8") as shown in
the picture.
Wrap the connected part between the Outdoor joint and the gas side of the outdoor unit
to prevent it from defrosting.
Wrap here with a
vinyl tape
Use EPDM insulation.
Pipe insulation
(Purchased individually)
90°
Insulation
( Purchased
individually)
Pipe
Pipe insulation
(Purchased individually)
ø D
ø D
90°
100mm or more
Cut the insulation at the
proper angle.
Cut the insulation
at the proper angle.
Insulation
Adhesive insulation
tape
Insulation for the
refrigerant pipe
Insulation for
the header joint
Insulation after welding a stopper
Adhesive insulation tape
Fix the header joint after insulating it.
DVM PLUS3 HR_IM_E_32805-2.indd 40 2011-11-11 오후 4:18:30