AA
12
When installing more than 1 outdoor unit
When 3 sides of the outdoor unit are blocked by the wall
300 or more
300 or more 600 or more 600 or more 600 or more
When the walls are blocking front and the rear of the outdoor units
300 or more1500 or more
600 or more 600 or more
When front and rear side of the outdoor unit is toward the wall
1500 or more 600 or more 3000 or more 3000 or more3000 or more
Unit: mm
Selecting installation location
Warning
• Should adopt bar type louver. Don’t use a type of rain resistance louver.
[Bar type louver] [Rain resistance louver]
• Louver specications.
- Angle criteria : less than 20˚