Preparations for Installation
Optional accessories
The following accessories are needed when connecting the outdoor and indoor unit.
Model Model Total capacity
Y-joint
MXJ-YA1509M 15.0 kW and below
MXJ-YA2512M Over 15.0 kW ~ 40.0 kW and below
Distribution header
MXJ-HA2512M 45.0 kW and Below (for 4 rooms)
MXJ-HA3115M 70.3 kW and below (for 8 rooms)
Refrigerant distributor component has to be installed when connecting indoor unit with no built-in EEV (electronic
expansion valve)
Decide the installation location, with the consideration of the following conditions, under users approval.
Place where hot discharge air or noise from the outdoor unit may not disturb the neighbor (Especially in residential
areas, keep the operation hours in mind.)
Place where structure can bear the weight and vibration of the outdoor unit.
Place with at surface where rainwater does not settle or leak.
Place where it is not exposed to strong wind.
Well ventilated place with sufficient service place for repairs and maintenance. (Discharge duct can be purchased
separately)
Place where you can connect the refrigerant pipes between indoor and outdoor units within allowable distance.
Place where it allows easy waterproong and draining work for the condensation water generated from the outdoor
unit during heating operation.
Place where there is no risk of inammable gas leakage.
Place where there is no direct inuence of snow or rain.
Do not install the product in a place where it will be directly exposed to sea breeze.
- Consult an installation expert (or company) since you will need to take extra anti-corrosion measures if you need to
install the product in a place where it can be exposed to direct sea breeze. (You have to remove dusts and salinity on
the heat exchanger and apply designated rust inhibitor more than once a year.)
If the outdoor unit is installed in the location where it can be attacked by high wind, please pay attention to these
issues:
- Caution when outdoor unit air outlet side was blow by high wind that speed over 5m/s, Because the outlet air was
suctioned in once again, reduce the airow of machine, and may cause these appearance:
- Lower capacity; -severe frost in heating mode; - machine break down for high pressure .
If the air outlet side of the outdoor unit encountered a large continuous strong wind blowing, the fan will run reversely
with high speed, and may be damaged by it. so please refer to the installation instruction.
Selecting installation location