EasyManua.ls Logo

Samsung DVM S ECO AM XMDG Series - Wiring work for air conditioner installation; Circuit breaker and power cable specifications

Samsung DVM S ECO AM XMDG Series
65 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
33
AA
ENGLISH
DVM S ECO Series
Wiring work
Caution
Caution for electrical work
You must install ELCB or MCCB + ELB
- ELCB: Earth leakage breaker
- MCCB: Molded case circuit breaker
- ELB: Earth leakage breaker
Do not operate the outdoor unit before completing the
refrigerant pipe work.
Do not disconnect or change the cable inside the product. It may cause damage to the product.
Specication of the power cable is selected based on following installation condition; culvert installation/
ambient temperature 30 °C/ single multi conductor cables. If the condition is different from the ones stated,
please consult an electrical installation expert and re-select the power cable.
- If the length of power cable exceed 50m, re-select the power cable considering the voltage drop.
Use a power cable made out of incombustible material for the insulator (inner cover) and the sheath (outer
cover).
Do not use the power cable with the core wire exposed due to insulator damage occurred during removal of
the sheath. When the core wire is exposed, it may cause re.
MCA: Minimum Circuit Ampere;
MFA: Maximum Fuse Ampere
Please refer to the MCA specication to selecte the line parameter.
Please refer to the MFA specication to selecte the MCCB and ELB specication.
Power Supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed exible
cord. (Code designation IEC:60245 IEC 66 / CENELEC: H07RN-F)
Capacity (HP) Model MCA (A) MFA (A)
8
AM080FXMDG
18.0 25.0
9
AM090FXMDG
18.5 25.0
8
AM080MXMDG
18.4 25.0
Specication of the circuit breaker and power cable
Insulator
(Inner
cover)
Exposed
core
(Example of exposed core)
Sheath
(Outer
cover)
This device is intended for the connection to a power supply system with a maximum permissible system impedance
shown in the table (on the left page) at the interface point (power service box) of the users supply.
The user must ensure that this device is connected only to a power supply system which fullls the requirement above.
If necessary, the user can ask the public power supply company for the system impedance at the interface point.
This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or equal to
Ssc(*2) at the interface point between the users supply and the public system. It is the responsibility of the installer
or user of the equipment to ensure, by consultation with the distribution network operator if necessary, that the
equipment is connected only to a supply with a short-circuit power Ssc greater than or equal to Ssc(*2).
[Ssc (*2)]
Capacity (HP) Model Ssc [MVA]
8
AM080
XMDG
3.4

Table of Contents

Related product manuals