K1(Number of press) KEY operation Display on segment
1 time Refrigerant charging in Heating mode
(Note 1)
““K” ”1” “BLANK” “BLANK”
2 times Trial operation in Heating mode
(Note 1)
“K” ”2” “BLANK” “BLANK”
3 times Pump out in Heating mode
(Note 1)
“K” ”3” “BLANK” “1”
4 times Vacuumig “K” ”4” “BLANK” “1”
5 times End Key operation —
K2(Number of press) KEY operation Display on segment
1 time Refrigerant charging in Cooling mode “K” ”5” “BLANK” “BLANK”
2 times Trial operation in Cooling mode “K” ”6” “BLANK” “BLANK”
3 times Pump down in Cooling mode “K” ”7” “BLANK” “BLANK”
4 times
Automatic setting of operation mode
(Cooling/Heating) for trial operation
“K” ”8” “BLANK” “BLANK”
5 times Checking the amount of refrigerant
“K” “9” “X” “X”
(Display of last two digits may differ
depending on the progress)
6 times Discharge mode of DC link voltage “K” ”A” “BLANK” “BLANK”
7 times Forced defrost operation
(Note 1)
“K” ”B” “BLANK” “BLANK”
8 times Forced oil collection “K” ”C” “BLANK” “BLANK”
9 times Inverter compressor check “K” ”D” “BLANK” “BLANK”
10 times End Key operation -
(Note 1) Not available on AM***FXM**C Series
K1 Control KEY operation Display on segment
Press and hold 1 time Auto trial operation “K” ”K” “BLANK” “BLANK”
Setting key operation and checking the view mode with tact switch
Setting outdoor unit option switch and key function
K1
K2