K3(Number of press) KEY operation Display on segment
1 time Intialize (Reset) setting Same as initial state
K4 (Press and hold to enter
the setting) K4 press
(Number of press)
Displayed content
Display on segment
Page 1 Page 2
0 time Main version MAIN Ver. (ex) 1412)
1 time Inverter version INV1 Ver. (ex) 1412)
2 times EEP version EEP Ver. (ex) 1412)
3 times Assigned address of the units AUTO
SEG 1,2 SEG 3,4
Indoor unit: A" , "0" Address (ex) 07)
4 times
Manually assigned address of
the units
MANU
SEG 1,2 SEG 3,4
Indoor unit: A" , "0" Address (ex) 15)
Even when the outdoor unit power is off, it is dangerous when you come in contact with inverter PCB since it is charged
with high DC voltage.
When replacing/repairing the PCB, cut-off the power and wait until the DC voltage is discharged before replacing/
repairing them. (Wait for more than 15 minutes to allow it to discharge naturally.)
When there were error, 'Dicharge mode of DC link voltage' may not have been effective. Especialy if error E464 has been
occured, power element might be damaged by re and therefore, do not use the 'Discharge mode of DC link voltage'.
During "Discharge mode of DC link voltage", voltage of INV will be displayed.