56
AA
K4(Number
of press)
KEY operation
Display on segment
SEG 1 SEG2, 3, 4
1 time Outdoor unit model 1
AM090FXM → 0, 0, 9
2 times Order frequency of compressor 2
120 Hz
→
1,2,0
3 times High pressure 3
1.52 MPa → 1, 5, 2
4 times Low pressure 4
0.43 MPa → 0, 4, 3
5 times Discharge temperature of compressor 5
87
°C
→ 0, 8, 7
6 times IPM temperature of compressor 6
87
°C
→ 0, 8, 7
7 times CT sensor value of compressor 7
2 A → 0, 2, 0
8 times Suction temperature 8
-42
°C
→ -, 4, 2
9 times COND OUT temperature 9
-42
°C
→ -, 4, 2
10 times Liquid pipe temperature A
-42
°C
→ -, 4, 2
11 times TOP temperature of compressor B
87
°C
→ 0, 8, 7
12 times Outdoor temperature C
-42
°C
→ -, 4, 2
13 times
EVI inlet temperature
D
-42
°C
→ -, 4, 2
14 times
EVI outlet temperature
E
-42
°C
→ -, 4, 2
15 times
Main EEV step
F
2000 steps
→
2, 0, 0
16 times EVI EEV step G
300 steps
→
3, 0, 0
17 times
Fan step
H
13 steps
→
0, 1, 3
18 times
Current frequency of compressor
I
120 Hz
→
1,2,0
19 times
Master indoor unit address
J
Master indoor unit not seleted
→
BLANK , N , D
If indoor unit No.1 is seleted as the master unit
→
0 , 0 , 1
Setting outdoor unit option switch and key function