Installation of refrigerant Y-joint
Install the Y-joint horizontally or vertically.
Install horizontally
Install vertically
When using A-J type of Y-joint,connect the Y-joint to the pipe with the provided reducer.
When using K-Z type of Y-joint,connect the Y-joint to the pipe by cutting the inlet of the Y-joint or provided reducer
properly.
≥10~15mm
Caution
Install the Y-joint within ±15° on the horizontal or on the vertical.
Make sure that the pipe does not break at Y-joint adn pipe connection.
Keep a minimum straight line distance of 500mm or more before connecting Y-joint.
Install the Y-joint within ±15° on the
horizontal or on the vertical.
Minimum straight line distance
(500mm or more)
Main pipe
Connect to outdoor unit
Pipe
Front
Rear
Rear
Pipe Connection
Reducer
Connect to other branch joint or
indoor unit
Reducer
Installation of Air-conditioner