AA
46
Pipe insulation
Fix the distribution header with a cable tie and cover the connected part.
Insulate the distribution header and the welded part and wrap the connected part with an
adhesive insulation tape to prevent dew formation.
Insulation
Adhesive insulation tape
Insulate the refrigerant
pipe
Insulate the
distribution header
Insulate after welding a stopper
Adhesive insulation tape
Fix the distribution header with a hanger after insulating it.
Insulating the branchjoint
Tightly attach the insulator, provided with the branch joint, to the separately purchased insulator. Wrap the connected
part with an insulator (separately purchased item) that has thickness of at least 10mm.
Use an insulator that resist heat up to 120°C. Wrap the branch joint with an insulation that has thickness of at least
10mm.
Fix securely without any gap.
Provided Insulator
Fix securely without
any gap.
Pipe insulator
(Separately
purchased item)
Pipe insulator (Separately
purchased item)
150mm
Branch joint
Thickness of the insulator (Separately purchased
item) should be thicker than 10mm.
Insulation tape (Separately purchased item)
Pipe insulator (Separately purchased item)
Pipe
Attach the adhesive insulation tape to
the pipe, as shown in the picture, after
insulating the pipe.
Insulate the distribution header

Table of Contents