Charging refrigerant
Important information regulation regarding the refrigerant used
This product contains uorinated greenhouse gases. Do not vent gases into the atmosphere.
Caution
• Inform user if the system contains 5 tCO2e or more of uorinated greenhouse gases. In this case, it must be
checked for leakage at least once every 12 months, according to regulation No. 517/2014. This activity must be
covered by qualied personnel only. In the case of the situation above, the installer (or authorized person with
responsibility for nal check) must provide a maintenance book, with all the information recorded, according
to REGULATION (EU) No. 517/2014 OF THE EUROPEAN PARLIAMENT AND OF THE COUNCIL of 16 April 2014 on
uorinated greenhouse gases.
Please ll in the following with indelible ink on the refrigerant charge label supplied with this product and on this manual.
①
the factory refrigerant charge of the product.
②
the additional refrigerant amount charged in the eld.
①
+
②
the total refrigerant charge.
The refrigerant charge label supplied with the product.
a Factory refrigerant charge of the product: see unit name plate.
b Additional refrigerant amount charged in the field. (Refer to the above information for the quantity of refrigerant
replenishment.)
c Total refrigerant charge.
d Refrigerant cylinder and manifold for charging.
Caution
• The lled-out label must be adhered in the proximity of the product charging port.
(ex. onto the inside of the stop valve cover.)
d
Indoor unit
Outdoor
unit
②
①
Refrigerant type GWP value
R-410A
2088
• GWP=Global Warming Potential
• Calculating
tCO
2
e
: kg x GWP / 1000
Unit Kg tCO
2
e
①, a
②, b
①+②, c