Connecting the ared pipes
Check if the aring is properly done according to the standard size.
Align the center of the piping and tighten the are nut with your hands. Then, tighten the are nut with torque wrench
in a direction of the arrow indicated in below illustration.
Make sure to use ester oil to coat the are connection section.
Pipe
Flare nutFlare connection section
Monkty
wrench
Torque
wrench
Outside
Diameter
(mm)
Connection
torque
(N·m)
Expansion
dimension
(mm)
Expansion specication
Ø
6.35 1.46~1.76 8.7~9.1
R 0.4~0.8
90° ±
45°
±
Ø
9.52 3.35~4.09 12.8~13.2
Ø
12.70 5.08~6.18 16.2~16.6
Ø
15.88 6.33~7.73 19.3~19.7
Installation of Air-conditioner
Blowing Nitrogen gas should be done when welding the pipe.
Make sure to use the provided are nut.
Make sure that there are no cracks or twisted part when you need to bend the pipe.
Do not fasten the are nut with excessive strength.
R-410A is a high pressure refrigerant and there is a risk of refrigerant leakage if the are connection is not
coated with ester oil. Therefore, apply ester oil to coat the are connection area.
Caution