EasyManua.ls Logo

Samsung DVM S ECO AM XMDG Series - Calculating total additional refrigerant amount

Samsung DVM S ECO AM XMDG Series
65 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
AA
20
Installation of Air-conditioner
m01 * 25.9Ø
536Ø
m01*
m5 * 25.9Ø
6Ø
.
53
*
m01
*HEDTNF630MA*HED4NF170MA
m5 * 25.9Ø
m5 * 53.6Ø
m5 * 53.6Ø
*HED4NF540MA
*HEDTNF630MA
m01 * 53.6Ø
m5 * 53.6Ø
*HEDTNF630MA
Method to calculate total amount of additional refrigerant
Total amount of additional refrigerant
Total amount of additional refrigerant = Amount of additional refrigerant depending on the pipe length
+ Amount of additional refrigerant for each indoor unit
Amout of additional refrigerant depending on the pipe length
Size of Liquid pipe
(mm)
Length(m)
Unit amount of refrigerant
(kg/m)
Amount of additional
refrigerant (kg)
Total amount
of additional
refrigerant (kg)
Ø6.35
20 0.02 0.4
1.75
Ø9.52
20 0.06 1.2
EEV kit ~ indoor unit 15 0.01 0.15
Amount of additional refrigerant charging for each indoor unit
Model name of
Indoor unit
Number of
units (EA)
Unit amount of refrigerant
(kg/m)
Amount of additional
refrigerant (kg)
Total amount
of additional
refrigerant (kg)
AM045FN4DEH*
1 0.45 0.45
1.62
AM071FN4DEH*
1 0.45 0.45
AM036FNTDEH* 3 0.24 0.72
Total amount of additional refrigerant = 1.75 + 1.62 = 3.37 (kg)