Field Setting Mode
Main Code Menu
Function
Sub
Code
MODEL CODE : AE***DN*MPK /
AE***DN*SPG / MIM-E03FN
MODEL CODE : AE***DN*THP
Setting Standard Setting Standard
Item Step Unit Default Min. value Max. value Default Min. value Max. value
Others
Code 50**
Addition
Function
Smart
Grid
Control
Application 1 - 5091 0 (No) 0 1 (Yes) 0 (No) 0 1 (Yes)
Setting Temp Shift
Value(Heating)
1  5092 2 1 50 2 1 50
Setting Temp Shift
Value(DHW)
1  5093 5 1 40 5 1 40
DHW Mode (Target Tank
Temp.)
1 - 5094 0 0 1 0 0 1
Others
Code 60**
Outdoor
Unit
Heating
Outdoor
Unit
Control
DHW Defrost Temp 1  6011 40 10 70 40 10 70
Mini Thermo ON
operating time limit
1 min 6022 5 5 30 5 5 30
Optional Thermo On/Off 1 - 6031 1 (Yes) 0 (No) 1 (Yes) 1 (Yes) 0 (No) 1 (Yes)
Thermostat
Control
Type
0 : 2way valve
"1" : Water pump
1 - 6041
1
(*5)
0
(*5)
1
(*5)
1
(*5)
0
(*5)
1
(*5)
0
(*6)
0
(*6)
1
(*6)
0
(*6)
0
(*6)
1
(*6)
Backup
Heater
Use in DHW Operation 1 - 6051
1 (Yes)
(*3)
0 (No)
(*3)
1 (Yes)
(*3)
1 (Yes)
(*3)
0 (No)
(*3)
1 (Yes)
(*3)
0 (No)
(*4)
0 (No)
(*4)
1 (Yes)
(*4)
0 (No)
(*4)
0 (No)
(*4)
1 (Yes)
(*4)
NOTE
(*3)
: Applies to the AE200DN**** model.
(*4)
: Applies to the AE160DN****/MIM-E03FN models.
(*5)
: Applies to the AE***DNX***/AE***DNZ*** models.
(*6)
: Applies to the AE***DNW***/AE***DNY***/MIM-E03FN models.