Operating advanced function _35
Remote Controller Setting Range : Code 10
✴✴
Space Cooling
Target water outlet temperature : Upper limit(#1011, Default 25ºC, Range : 18 ~ 25ºC),
Lower limit(#1012, Default 16ºC, Range : 5 ~ 18ºC)
- With this default FSV settings, user can change the target water outlet temperature within
the range of 5 ~ 25ºC for cooling
Target room temperature : Upper limit(#1021, Default 30ºC, Range : 24 ~ 30ºC),
Lower limit(#1022, Default 18ºC, Range : 18 ~ 22ºC)
- With this default FSV settings, user can change the target room temperature within the
range of 18 ~ 30ºC for cooling.
The #1 DIP switch in the wired remote controller should be set to “OFF”(Default) for
cooling operation of heat pump.
The #2 DIP switch in the wired remote controller should be set to “OFF”(Default) to
control the water outlet temperature.
The #2 DIP switch in the wired remote controller should be set to “ON” to control the
room temperature.
The #3 DIP switch in the wired remote controller should be set to “OFF”(Default) to
control the air sensor in remote controller.
Space Heating
Target water outlet temperature : Upper limit(#1031, Default 55ºC, Range : 37 ~ 55ºC),
Lower limit(#1032, Default 25ºC, Range : 15 ~ 37ºC)
- With this default FSV settings, user can change the target water outlet temperature within
the range of 25 ~ 55ºC for heating.
Target room temperature : Upper limit(#1041, Default 30ºC, Range : 24 ~ 30ºC),
Lower limit(#1042, Default 16ºC, Range : 16 ~ 22ºC)
- With this default FSV settings, user can change the target room temperature within the
range of 16 ~ 30ºC for heating.
The #2 DIP switch in the wired remote controller should be set to “OFF”(Default) to
control the water outlet temperature.
The #2 DIP switch in the wired remote controller should be set to “ON” to control the
room temperature.
Field Setting Value
Main Menu &
Code
Sub Menu Function
Description
Sub
Code
Default
Min
Max
Step
Unit
Remote
Controller
Setting Range
Code 10
✴✴
Water Out Temp for Cooling
Max
✴✴
11
25
18
25
1
˚C
Min
✴✴
12
16
5
18
1
˚C
Room Temp for Cooling
Max
✴✴
21
30
24
30
1
˚C
Min
✴✴
22
18
18
22
1
˚C
Water Out Temp for Heating
Max
✴✴
31
55
37
55
1
˚C
Min
✴✴
32
25
15
37
1
˚C
Room Temp for heating
Max
✴✴
41
30
24
30
1
˚C
Min
✴✴
42
16
16
22
1
˚C
DHW Tank Temp
Max
✴✴
51
50
50
65
1
˚C
Min
✴✴
52
40
30
40
1
˚C
DHW Heating
Target DHW tank temperature : Upper limit(#1051, Default 50ºC, Range : 50 ~ 80ºC),
Lower limit(#1052, Default 40ºC, Range : 30 ~ 40ºC)
- With this default FSV settings, user can change the target tank temperature within the
range of 40 ~ 50ºC for DHW heating.
The FSV #3011 in the wired remote controller should be set to “1(Yes)” to use DHW
function.
The #3 DIP switch in the wired remote controller should be set to “ON” to control the
external air sensor.