4th Edition of TEMI880 IM : Jan. 29. 2007 Page 98 / 119
4.3.8 STD Command
This command is register D-Register which you want to using at the TEMI880.
Transmission Format
Byte 1 2 3 1 2 1 4 1 4 1
S
T
Command
element
X
Addr STD ,
Para.
number
, D-Reg. No1 , D-Reg. No2 ,
1 4 1 4 2 1 1
C L
, D-Reg. No(n-1) , D-Reg. No(n) SUM
R F
Response
Byte 1 2 3 1 2 2 1 1
S
T
Command
element
X
Addr STD , OK SUM
C
R
L
F
- Para. number : 1~32.
ex) When the registration Temp. PV(D0001), Temp. SP(D0002), Humi. PV(D0005), Humi. SP(D0006).
- Transmission : [stx]01STD,04,0001,0002,0005,0006[cr][lf]
- Transmission(Include Check Sum) : [stx]01STD,04,0001,0002,0005,00069A[cr][lf]