EasyManua.ls Logo

Samwon Tech TEMI880 - D-Register Explanation

Default Icon
122 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SAMWONTECH
4th Edition of TEMI880 IM : Jan. 29. 2007 Page 100 / 119
4.4 D-Register Explanation
D-Register is group of data which can use with communication all of TEMI880’s condition.
Each group has 100 registers and these are classified as follows.
D-Register Range Group Name Description Read Write
D0001~D0099 PROCESS Basic process display X
D0100~D0199 FUNCTION Operation information display
D0200~D0299 RESERVATION Time & Reservation
D0300~D0399 ON OFF / IS ON/OFF & Inner signal
D0400~D0499 ALARM / TS Alarm & Time signal
D0500~D0599 TEMP PID Temp. P.I.D
D0600~D0699 HUMI PID Humi. P.I.D
D0700~D0799 COMM Communication X
D0800~D0899 OUTPUT Output
D0900~D0999 INPUT Input
D1000~D1099 PROGRAM Program
D1100~D1199 RESERVED Blank X X
D1200~D1299 RESERVED Blank X X
D1300~D1399 FILE1 Display Temp. TSP of segment X
D1400~D1499 FILE2 Display Humi. TSP of segment X
D1500~D1599 FILE3 Display setting time of segment X
D1600~D1699 PROG_INFO Basic information of program pattern
D1700~D1799 FILE4 Set TS1 of segment X
D1800~D1899 FILE5 Set TS2 of segment X
D1900~D1999 FILE6 Set TS3 of segment X
D2000~D2099 FILE7 Set TS4 of segment X
D2100~D2399 RESERVED Blank X X
Each D-Register is consisted of hexadecimal 4 characters(2-Byte).

Related product manuals