SAMWONTECH
4th Edition of TEMI880 IM : Jan. 29. 2007 Page 105 / 119
4.4.4 Set Program Pattern
4.4.4.1 Program
Program group is consisted of program pattern setting D-Registers.
How to set a program pattern is :
Set one by one with changing number of segment on TEMI880.
Program pattern setting D-Register
D-Reg. Symbol Value Description
D1000 P_PTNO 1~120 Set program pattern number to Read or Write
D1001 DEST_PTNO 1~120 Set pattern number to be copied
0 Set to Read or Write on D1603~D1618
D1002 P_SEGNO
1~99 Set segment to Read or Write
1 INIT : D1000~D1004 value set '0'
2 READ : Reading value of D1000 and D1002
3 WRITE : Writing value of D1000 and D1002
4 PT COPY : Copy pattern D1000 to D1001
5 PT DEL : Delete pattern on D1000
6 SEG INSERT : Insert segment on D1000 and D1002
7 SEG DEL : Delete segment on D1000 and D1002
D1003 TRIGGER
8 ALL PT : Display pattern of D1000 to D1300 ...
0 FULL : Full memory for pattern or segment
1 DONE : Complete D1003(TRIGGER)’s job
2 PT EMPTY : Empty pattern
3 SEG EMPTY : Empty segment
4 PT RUN : PROG RUN Status
5 PARA ERROR : Setting error on D1000~D1003
D1004 ANSWER
6 PT USED : PROG RUN by pattern
D1010 TEMP_TSP - Temp. TSP(Target Set Point) to Read or Write
D1011 HUMI_TSP - Humi. TSP(Target Set Point) to Read or Write
D1012 SEG_TIME - Segment time to Read or Write
D1013 TS1 - Time signal 1 to Read or Write
D1014 TS2 - Time signal 2 to Read or Write
D1015 TS3 - Time signal 3 to Read or Write
D1016 TS4 - Time signal 4 to Read or Write