SAMWONTECH
4th Edition of TEMI880 IM : Jan. 29. 2007 Page 85 / 119
2.12.2.1 Set Control Output
Symbol Parameter Setting Range Unit Init. Value
OUTPUT TYPE
TEMP OUTPUT
TYPE
SSR, SCR ABS SSR
DIRECTION
TEMP OUTPUT
DIRECTION
REV, FWD ABS REV
CYCLE TIME
TEMP SSR
CYCLE TIME
1~300 SEC ABS 1
TEMP ARW SET
TEMP ANTI RESET
WIND-UP
0.0(AUTO), 0.0~200.0 ABS 100.0
TEMP AT-GAIN
TEMP AUTO
TUNING GAIN
0.1~10.0 ABS 1.0
OUTPUT TYPE
HUMI OUTPUT
TYPE
SSR, SCR ABS SSR
DIRECTION
HUMI OUTPUT
DIRECTION
REV, FWD ABS REV
CYCLE TIME
HUMI SSR
CYCLE TIME
1~300 SEC ABS 1
HUMI ARW SET
HUMI ANTI RESET
WIND-UP
0.0(AUTO), 0.0~200.0 ABS 100.0
HUMI AT-GAIN
HUMI AUTO
TUNING GAIN
0.1~10.0 ABS 1.0
2.12.2.2 Set Transmission Output
Symbol Parameter Setting Range Unit Init. Value
TEMP RET.
TEMP
RETRANSMISSION
PV, SP, MV ABS PV
TEMP RET. RH
TEMP RET.
RANGE HIGH
T.EU T.EU(100%)
TEMP RET. RL
TEMP RET.
RANGE LOW
T.EU(0~100%)
TEMP RET RL
< TEMP RET RH
T.EU T.EU(0%)
HUMI RET.
HUMI
RETRANSMISSION
PV, SP, MV ABS PV
HUMI RET. RH
HUMI RET.
RANGE HIGH
H.EU H.EU(100%)
HUMI RET. RL
HUMI RET.
RANGE LOW
H.EU(0~100%)
HUMI RET RL
< HUMI RET RH
H.EU H.EU(0%)