I - 19
SM830082
1
2
3
4
5
1. Specifications
MODEL No. UH3642
Source 230 - 208 V / 1 phase / 60 Hz
Remote controller (Option) RCS - BH80UA, WL
Controller P. C. B Ass'y CR - TH2442
Control circuit fuse 250 V, 3 A
Fan (Number … diameter) in. (mm) Centrifugal (4 ... 5-29/32(150))
Fan motor
Model KFG4X - 141A6P
Source 230 - 208 V / 1 phase / 60 Hz
No. of pole … r.p.m. (230 V, High) rpm 4 ... 940
Nominal output W 100
Coil resistance BRW - WHT : 39.9 , ORG - YEL : 9.37
(Ambient temperature 68 °F) WHT - VLT : 6.91 , YEL - BLK : 8.86
VLT - ORG : 11.4 , BLK - PNK : 14.3
Safety device
Operating temperature Open °F266± 14.4
Close °F 174.2 ± 27
Run capacitor VAC, µF 440 V , 5 µF
Electronic expansion valve
Coil DKV - MOZS698E0
Coil resistance ORG - GRY : 46 , YEL - GRY : 46
(Ambient temperature 68 °F) RED - GRY : 46 , BLK - GRY : 46
Valve body HKV - 30D27
Heat exchanger
Coil Aluminum plate fin / Copper tube
Rows … Fins per inch 3 … 12.7
Face area ft.
2
(m
2
) 3.32 (0.308)
DATA SUBJECT TO CHANGE WITHOUT NOTICE