I - 20
SM830082
1
2
3
4
5
1. Specifications
1-2 Major Component Specifications
(A) Indoor Unit
MODEL No. KH2442
Source 230 - 208 V / 1 phase / 60 Hz
Remote controller (Option) RCS - BH80UA, WL
Controller P. C. B Ass'y CR - TH2442
Control circuit fuse 250 V, 3 A
Fan Cross-flow
Number ... Dia. and length in. (mm) 1 ... O.D. 4-1/3 (110), L39 (990)
Fan motor
Model UF4Q - 31A6P
Source 230 - 208 V / 1 phase / 60 Hz
No. of pole … r.p.m. (230 V, High) rpm 4 ... 1,276
Nominal output W 30
Coil resistance BRW - WHT : 197.2 , ORG - YEL : 59.1
(Ambient temperature 68 °F) WHT - VLT : 41.4 , YEL - PNK : 48.8
VLT - ORG : 22.2 ,
Safety device
Operating temperature Open °F248± 9
Close °F171± 27
Run capacitor VAC, µF 440 V , 1.8 µF
Electronic refrigerant control valve
Solenoid control model DKV - MOZS582E0
Coil resistance ORG - GRY : 46 , YEL - GRY : 46
(Ambient temperature 68 °F) RED - GRY : 46 , BLK - GRY : 46
Solenoid control valve model IKV - 24D11
Heat exchanger
Coil Aluminum plate fin / Copper tube
Rows … 3 … 12.7
Face area ft.
2
(m
2
) 2.57 (0.24)
Louver Motor
Model M2EA24ZA01
Rating 208 to 230 V, 60 Hz
No. of pole … rpm 8 … 3
Output W 2.5
Coil resistance (Ambient temperature 68 °F) k 16.45 ± 8 %
DATA SUBJECT TO CHANGE WITHOUT NOTICE