EasyManua.ls Logo

Sanyo SPW-CR605GXH8 - Page 301

Sanyo SPW-CR605GXH8
345 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4
4 - 159
Mini ECO-i SYSTEM Unit Specifications
10. Concealed Floor-Standing Type (FM Type)
Indoor unit (C)
MODEL No. SPW-FMR124GXH56(A/B)
Power source
220 - 230 - 240 V / Single-phase / 50 Hz
Controller P.C.B. Ass’y
CR-TRP50A-B (Microprocessor)
Fan (Number…diameter) mm
Centrifugal (1 … ø 153)
Fan motor
Model…Nominal output W
KFT4Q-21B3P … 30 W
Power source 220 - 230 - 240 V / Single-phase / 50 Hz
No. of pole…r.p.m. (230 V, High) rpm 4P … 1,102
Coil resistance BRN WHT : 217.7 ORG YEL : 37.88
(Ambient temperature 20°C) WHT VLT : 37.33 YEL PNK :
21.82
VLT ORG :
22.48
Safety device
Operating temperature Open °C 130 ± 5
(115 ± 5)
Close
°C
Run capacitor VAC, µF 440 VAC, 2.0 µ
F
Electronic expansion valve
Coil UKV-U030E
Coil resistance (at 20°C) ORG GRY : 46 YEL GRY : 4
6
RED GRY : 46 BLK GRY : 4
6
Valve body
UKV-18D31
Heat exchanger
Coil
Aluminum plate fin / Copper tube
Rows…fin pitch mm 3…2.0
Face area m
2
0.102
06-405 Mini-ECOi_TD4 11/8/06 4:28 PM Page 159

Table of Contents

Related product manuals