Sanyo SPW-CR605GXH8 - Electrical Wiring; General Precautions on Wiring; Recommended Wire Length and Wire Diameter for Power Supply System

Sanyo SPW-CR605GXH8
345 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2
Design of Mini ECO-i SYSTEM
4. Electrical Wiring
Control wiring
(C) Inter-unit (between outdoor and
indoor units) control wiring
(D) Remote control wiring (E) Control wiring for group control
0.75 mm
2
(AWG #18)
0.75 mm
2
(AWG #18)
0.75 mm
2
(AWG #18)
Use shielded wiring* Use shielded wiring Use shielded wiring
Max. 1,000 m
Max. 500 m
Max. 500 m (Total)
4-1. General Precautions on Wiring
(1) Before wiring, confirm the rated voltage of the unit
as shown on its nameplate, then carry out the
wiring closely following the wiring diagram.
(2) Provide a power outlet to be used exclusively for
each unit, and a power supply disconnect and
circuit breaker for overcurrent protection should
be provided in the exclusive line.
(3) To prevent possible hazards from insulation failure,
the unit must be grounded.
(4) Each wiring connection must be done in
accordance with the wiring system diagram.
Wrong wiring may cause the unit to misoperate
or become damaged.
(5) Do not allow wiring to touch the refrigerant tubing,
compressor, or any moving parts of the fan.
(6) Unauthorized changes in the internal wiring can be
very dangerous. The manufacturer will accept no
responsibility for any damage or misoperation that
occurs as a result of such unauthorized changes.
(7) Regulations on wire diameters differ from locality
to locality. For field wiring rules, please refer to
your LOCAL ELECTRICAL CODES before
beginning.
You must ensure that installation complies with all
relevant rules and regulations.
(8) To prevent malfunction of the air conditioner
caused by electrical noise, care must be taken
when wiring as follows:
G The remote control wiring and the inter-unit control
wiring should be wired apart from the inter-unit
power wiring.
G Use shielded wires for inter-unit control wiring
between units and ground the shield on both sides.
(9) If the power supply cord of this appliance is
damaged, it must be replaced by a repair shop
appointed by the manufacturer, because special
purpose tools are required.
4-2. Recommended Wire Length and Wire Diameter for Power Supply System
Outdoor unit (Single-phase)
(A) Power supply
Wire size Max. length
SPW-CR365GX(H)56(A/B) 16 m 25 A
SPW-CR485GX(H)56(A/B) 24 m 35 A
SPW-CR605GX(H)56(A/B) 20 m 35 A
4 mm
6 mm
6 mm
2
2
2
Time delay fuse or
circuit capacity
Indoor unit
Time delay fuse or
circuit capacity
(B) Power supply
2.5 mm
2
K
AS, LD, S, X, T, U, F, FM
Type
Max. 150 m
Max. 130 m
Max. 60 m
10 – 16A
10 – 16A
10 – 16A
D
Outdoor unit (3-phase)
(A) Power supply
Wire size Max. length
SPW-CR365GXH8B50 m20 A
SPW-CR485GXH8B47 m20 A
SPW-CR605GXH8B47 m20 A
2.5 mm
2.5 mm
2.5 mm
2
2
2
Time delay fuse or
circuit capacity
NOTE
* With ring-type wire terminal.
2 - 34
06-405 Mini-ECOi_TD2 11/6/06 5:15 PM Page 34