Control of Mini ECO-i SYSTEM
2. Wireless Remote Controller
2-21. Wiring the Separate Receiver Unit
* Use wires that are 0.5 mm
2
– 2 mm
2
in diameter.
* The wiring length must not exceed 400 m.
<Flush Mounting>
<Exposed Mounting>
G Use the remote controller cord (optional) for wiring
the separate receiver unit.
1. For the methods used to install the remote con-
troller cord, refer to “For flush mounting into a
wall, install the separate receiver unit in a metal
switch box (field supply) that has been recessed
into the wall in advance” on P. 3-21.
2. When using the remote controller cord (optional),
refer to the instruction manual that came with the
cord.
Check the terminal number on the indoor unit
before wiring the remote controller and be sure
not to wire incorrectly. (The unit will be damaged if
high voltage, such as 200 VAC, is applied to it.)
1. Strip the insulation to approximately 14mm
from the ends of the wires to be connected.
2. Twist together the 2 wires and create a
crimp connection at the wire joint.
3. If a special crimping tool is not used, or if
wires using insulation tape.