EasyManuals Logo

Satec Expertmeter Series User Manual

Satec Expertmeter Series
169 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #25 background imageLoading...
Page #25 background image
Chapter 2 Installation Electrical Installation
EM13x Series SMART MULTIFUNCTION METER 25
2.4 Electrical Installation
The equipment installation shall conform to the following
instructions:
a) a switch or circuit-breaker shall be included in the building
installation as close as possible to the equipment supply
voltage;
b) It shall be in close proximity to the equipment and within
easy reach of the OPERATOR;
c) It shall be marked as the disconnecting device for the
equipment.
d) Before installing, ensure that all incoming power sources are
shut OFF. Failure to observe this practice can result in serious
or even fatal injury and damage to equipment.
e) The current sensors may not be installed in a panel where
they exceed 75% of the wiring space of any cross-sectional
area within the panel.
Connecting the wires
All conductors must be stranded copper. All conductors and insulation
systems and crimped devices must be appropriate for the application.
SATEC requires using crimped ferrules on stranded wire.
Table 3 below summarizes the different conductors’ sizes to be used in
the EM133 external connections.
Table 2: Wiring Configurations
Terminals
Conductor size
Torque
[Nm]
Notes
EM133 model
Minimum
AWG (mm²)
Maximum
AWG (mm²)
Aux. Power
Supply Inputs
L/+, N/-
N/A in EM133-
SE models
22 (0.5)
12 (4.0)
0.5-0.7
Use 600V insulated conductors
Required crimped ferrule:
Panduit (22AWG) F75-10-M
Panduit (12AWG) F81-15-M
Voltages Inputs
V1, V2, V3, Vn
N/A in EM133-
SE-100A
22 (0.5)
12 (4.0)
0.5-0.7
Use 600V insulated conductors
Required crimped ferrule:
Panduit (22AWG) F75-10-M
Panduit (12AWG) F81-15-M
Current Inputs
I1, I2, I3, N
EM133/SE-
1A, 5A, HACS
22 (0.5)
10 (6.0)
1.8-2
Use 600V insulated conductors
Required crimped ferrule:
Panduit (22AWG) F75-10-M
Panduit (10AWG) F82-15-M
Current Inputs
I1, I2, I3, N
EM133/SE-
100A
6 (16)
4 (25)
2-2.7
Use 600V insulated conductors
Required crimped ferrule:
Panduit (6AWG) F84-15-M
Panduit (4AWG) F85-15-M
COM1, I/O
connections
All Models
22 (0.5)
12 (4.0)
0.5-0.7
Use 600V insulated conductors
Required crimped ferrule:
Panduit (22AWG) F75-10-M
Panduit (12AWG) F81-15-M

Table of Contents

Other manuals for Satec Expertmeter Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Satec Expertmeter Series and is the answer not in the manual?

Satec Expertmeter Series Specifications

General IconGeneral
BrandSatec
ModelExpertmeter Series
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals