Measurements and Recording P746/EN MR/A11
MiCOM P746 (MR) 8-
13
MR
Setting Range
Menu Text Default Setting
Min. Max.
Step Size
Digital Input 2 Output R2 As above
The relay 2 output digital channel is assigned to this channel.
Input 2 Trigger No Trigger No Trigger, Trigger L/H, Trigger H/L
Digital Input 3 Output R3 As above
Relay 3 output digital channel.
Input 3 Trigger No Trigger No Trigger, Trigger L/H, Trigger H/L
Digital Input 4 Output R4 As above
Relay 4 output digital channel.
Input 4 Trigger No Trigger No Trigger, Trigger L/H, Trigger H/L
Digital Input 5 Output R5 As above
Relay 5 output digital channel.
Input 5 Trigger No Trigger No Trigger, Trigger L/H, Trigger H/L
Digital Input 6 Output R6 As above
Relay 6 output digital channel.
Input 6 Trigger No Trigger No Trigger, Trigger L/H, Trigger H/L
Digital Input 7 Output R7 As above
Relay 7 output digital channel.
Input 7 Trigger No Trigger No Trigger, Trigger L/H, Trigger H/L
Digital Input 8 Output R8 As above
Relay 8 output digital channel.
Input 8 Trigger No Trigger No Trigger, Trigger L/H, Trigger H/L
Digital Input 9 Any Trip As above
Any trip
Input 9 Trigger Trigger L/H No Trigger, Trigger L/H, Trigger H/L
Digital Input 10 Ouput R10 As above
Relay 10 output digital channel.
Input 10 Trigger Trigger L/H No Trigger, Trigger L/H, Trigger H/L
Digital Input 11 Diff Fault Z1 As above
Busbar Differential Fault in Zone 1
Input 11 Trigger Trigger L/H No Trigger, Trigger L/H, Trigger H/L
Digital Input 12 Diff Fault Z2 As above
Busbar Differential Fault in Zone 2
Input 12 Trigger Trigger L/H No Trigger, Trigger L/H, Trigger H/L
Digital Input 13 Diff Fault CZ As above
Busbar Differential Fault in Check Zone
Input 13 Trigger Trigger L/H No Trigger, Trigger L/H, Trigger H/L
Digital Input 14 Idiff Start Z1 As above
Differential current in main zone 1.