Technical Data P746/EN TD/G31
MiCOM P746
(TD) 2-9
TD
Overcurrent Protection
Phase Fault Protection (50/51)
3 phase Overcurrent function Status I>1:
Disabled
DT
IEC S Inverse or IEC V Inverse or IEC E
Inverse
UK LT Inverse
IEEE M Inverse or IEEE V Inverse or IEEE
E Inverse
US Inverse or US ST Inverse
Current Set if “function status” 0
I>1: 0.10...32.00 xIn
Time delay if “function status”=1
I>1: 0.00...100.00 xIn
TMS if 2 ”function status” 5
I>1: 0.025...1.200 xIn (step 0.025)
Time dial if “function status”6
I>1: 0.5...15.0 xIn
Reset Char. if “function status”6
I>1:
DT
Inverse
tReset if 2”function status”5 OR if “Reset
Char.”=1 AND “function status”6
I>1: 0.0...100.0 xIn
3 phase Overcurrent threshold function status
I>2:
Disabled
Blocking 87BB
High set I>2
Both
Current Set
I>2: 0.10... 32.00
Time Delay if “function status”=1
I>2: 0.00...100.00 s
Earth Fault Protection (50N/51N) (One Box
Mode)
Residual Overcurrent Function Status I
N
>1:
Disabled
DT
IDG
RI
IEC S Inverse or IEC V Inverse or IEC E
Inverse
UK LT Inverse, UK Rectifier
IEEE M Inverse or IEEE V Inverse or IEEE
E Inverse
US Inverse or US ST Inverse
Current Set if “function status” 0
I
N
>1: 0.10...32.00 xIn
Time delay if “function status”=1
I
N
>1: 0.00...100.00 xIn
TMS if 2”function status”5
I
N
>1: 0.025...1.200 xIn (step 0.025)
Time dial if “function status”6
I
N
>1: 0.5...15.0 xIn
Reset Char. if “function status”6
I
N
>1:
DT
Inverse
tReset if 2”function status”5 OR if “Reset
Char.”=1 AND “function status”6
I
N
>1: 0.0...100.0
Residual Overcurrent threshold function status
I
N
>2:
Disabled
Blocking 87BB
High set I>2
Both
Current Set
I
N
>2: 0.10 xIn...32.00 xIn
Time Delay if “function status”=1
I
N
>2: 0.00...100.00 s
Supervision
Voltage transformer supervision:
Status:
Blocking & indication
Manual & automatic mode
Time delay:
1s...10.00s (step 100ms)
Current transformer supervision:
Status:
Blocking & indication
Setting accuracy: ±5%
Time delay:
0…10.00s (step 100ms)
accuracy: ±2% or 50ms (whichever is
greater)
CTS I1 / CTS I2/I1>1 / CTS I2/I1 >2:
5%...100% (step 1%)
Date and Time
IRIG-B Sync:
Disabled/Enabled
Battery Alarm:
Disabled/Enabled
Configuration
Setting Group:
. Select via Menu
. Select via Opto
Active Settings: Group 1/2/3/4
Setting Group 1: Disabled/Enabled
Setting Group 2: Disabled/Enabled
Setting Group 3: Disabled/Enabled
Setting Group 4: Disabled/Enabled
Dead zone OC Prot: Disabled/Enabled
Diff Busbar Prot: Disabled/Enabled
Overcurrent Prot: Disabled/Enabled
Earth Fault Prot: Disabled/Enabled
CB Fail & I>: Disabled/Enabled
Setting Values: Primary/Secondary
LCD Contrast: (Factory pre-set)
Fault Recorder
Records for the last 5 faults:
Indication of the faulty zone
Protection element operated
Active setting group
Fault duration
Currents and frequency
Faulty zone differential and bias current
Topology at the fault occurrence
Event Recorder
Records for the last 512 events