www.schiedel.com/uk
ICS
Installation Instructions
SCHIEDEL INSTALLER
REWARDS
DON'T FORGET TO REGISTER YOUR INSTALLATIONS
AND START EARNING SCHIEDEL INSTALLER REWARDS
See inside for more details
SAP 940002195 - October 2021
Question and Answer IconNeed help?

Do you have a question about the Schiedel ICS and is the answer not in the manual?

Schiedel ICS Specifications

General IconGeneral
BrandSchiedel
ModelICS
CategoryFan
LanguageEnglish

Summary

Approvals

Design Guide

MANDATORY REQUIREMENTS

Outlines essential rules and regulations for installation, including competent persons and certifications.

Prior to Installation

VENTILATION

Importance of sufficient air for combustion and ventilation, referencing regulations and guidance.

CARBON MONOXIDE ALARMS

Requirements for CO alarms, including siting and compliance with BS EN 50291.

PAINTING

Guidance on preparing surfaces and options for special order painted finishes.

HANDLING

Recommendation to use suitable Personal Protective Equipment (PPE) when handling.

DELIVERY TO SITE AND STORAGE

Instructions for safe transport, offloading, inspection, and storage of components.

Connecting Flue Pipe

APPLIANCE/CHIMNEY CONNECTION

How to connect flue pipes to appliances and the chimney system, sealing requirements.

CONNECTION TO DRAUGHT DIVERTER

Specific guidance for connecting to appliances with a draught diverter, vertical rise requirements.

CONNECTING FLUE PIPE DIAMETER

Guidance on selecting the correct flue diameter based on appliance and standards.

DISTANCE TO COMBUSTIBLES

Essential distances to combustible materials for connecting flue pipes as per regulations.

BS EN 15287-1

CONNECTING FLUE PIPE ROUTE

Guidelines for the placement and routing of connecting flue pipes to avoid hazards.

INSPECTION

Requirements for providing inspection and cleaning access points within the system.

Top Outlet Single Wall Connecting Flue Pipe through Solid Wall into Twin Wall System Chimney

Diagram showing connection of single wall flue pipe through solid wall to twin wall system.

Top Outlet Twin Wall Connecting Flue Pipe through Solid Wall into Twin Wall System Chimney

Diagram showing twin wall flue pipe connection through solid wall to twin wall system.

Top Outlet Twin Wall Connecting Flue Pipe into Re-lined Masonry Chimney

Diagram showing twin wall flue pipe connection into a re-lined masonry chimney.

Rear Outlet Twin Wall Connecting Flue Pipe into Re-lined Masonry Chimney

Diagram showing twin wall flue pipe connection into re-lined masonry chimney.

Rear Outlet Twin Wall Connecting Flue Pipe Through Cavity Wall into Twin Wall System Chimney

Diagram showing twin wall flue pipe connection through cavity wall to twin wall system.

Rear Outlet Twin Wall Connecting Flue Pipe into External Masonry Chimney through a Cavity Wall

Diagram showing twin wall flue pipe connection into external masonry chimney via cavity wall.

System Chimney

CHIMNEY DIAMETER

How to determine the correct chimney diameter based on appliance and standards.

CHIMNEY ROUTE

Guidelines for routing the chimney, including vertical runs and offsets.

CONNECTION TO DRAUGHT DIVERTER

Specific guidance for connecting to appliances with a draught diverter.

DIRECT CONNECTION APPLIANCE TO SYSTEM CHIMNEY

Instructions for directly connecting an appliance to the system chimney.

DISTANCE TO COMBUSTIBLES

Required distances to combustible materials for solid fuel, gas, and oil applications.

ENCLOSURE/SHAFTS

Requirements for enclosing chimneys passing through building elements to prevent contact.

SUPPORT COMPONENTS

Information on how to support the chimney system using various components.

CHIMNEY TERMINATION

Guidance on the correct termination of the chimney system at the roof level.

TERMINALS

Types of terminals available and their installation requirements.

Installation Instructions

JOINTING SYSTEM

Explains the ICS and ICS Plus jointing methods using locking bands and lip seals.

STANDARD CHIMNEY SECTIONS (PIPES, TEES AND ELBOWS)

Instructions for assembling standard chimney sections, ensuring correct direction.

LOCKING BAND (SUPPLIED WITH EACH COMPONENT WITH A FEMALE SOCKET ON THE CASE)

How to fit and secure the standard locking band for joint integrity.

STRUCTURAL LOCKING BAND

Use of structural locking bands for extra support in specific situations.

APPLIANCE CONNECTOR/STARTING CONNECTOR/STOVE STARTER PIPE

Installation of appliance connectors and stove starter pipes, including sealing.

ADAPTORS FROM PRIMA PLUS & PRIMA SMOOTH TO ICS

How to use adaptors to connect Prima Plus/Smooth flue pipes to the ICS system.

ADAPTOR TO FLEX/TECNOFLEX PLUS

How to connect ICS to Flex/TecnoFlex Plus systems using adaptors.

ADAPTOR FROM ICS TO PRIMA PLUS

How to connect ICS to Prima Plus systems using specific adaptors.

INCREASER

How to use an increaser component to change chimney diameter.

ANCHOR PLATE

Use of anchor plates for fire chests, hoods, or extending existing chimneys.

ADJUSTABLE PIPE

How to use and adjust the adjustable pipe for precise on-site length fitting.

INSPECTION LENGTH (DRY SYSTEMS)

Component for flue inspection and cleaning in dry systems.

INSPECTION LENGTH (CONDENSING SYSTEMS)

Component for flue inspection and cleaning in condensing systems.

INSPECTION PIPE

Component providing facility to inspect the flue.

MEASURE PIPE

Component for draught testing or flue gas analysis.

VERTICAL DRAIN PIPE

Component for collecting and draining condensate from condensing systems.

SW-DW ADJUSTABLE STARTER SECTION

How to install the adjustable starter section for thermal expansion and servicing.

ELBOWS AND 90° INSPECTION ELBOWS

Information on using elbows and inspection elbows, including vertical height requirements.

90° TEE

Use of 90° Tee for connecting flue pipe to chimney or draft stabilizer.

93° TEE

Use of 93° Tee for condensing systems to ensure condensate drainage.

135° TEE

Use of 135° Tee with 45° elbow for low resistance flue gas flow.

Double Wall Adjustable Starter Section

Initial installation

Detailed steps for fitting the double wall adjustable starter section correctly.

Removal of stove for servicing

Step-by-step instructions for safely removing the stove for maintenance.

Re-installation of stove after servicing

Detailed steps for correctly re-installing the stove after servicing.

Offset Dimensions

Offsets for Double 15° Bend

Offset dimensions for configurations using two 15° bends.

Offsets for Double 30° Bend

Offset dimensions for configurations using two 30° bends.

Offsets for Double 45° Bend

Offset dimensions for configurations using two 45° bends.

Offsets for Double 90° Bend

Offset dimensions for configurations using two 90° bends.

Offsets for 135 Tee° & 45° Bend

Offset dimensions for configurations using 135° Tee and 45° bend.

Double 15° Bend C/W Pipe Length

Effective pipe length for double 15° bend offsets.

Double 30° Bend C/W Pipe Length

Effective pipe length for double 30° bend offsets.

Double 45° Bend C/W Pipe Length

Effective pipe length for double 45° bend offsets.

Double 90° Bend C/W Pipe Length

Effective pipe length for double 90° bend offsets.

Firestop Components

VENTILATED SUPPORT PLATE (GALVANISED WITH S/S BAND)

Installation of the ventilated support plate for combustible floors.

VENTILATED FIRESTOP PLATE (1 & 2-PIECE ROUND AND 2-PIECE RECTANGULAR)

Use of ventilated firestop plates for combustible floors/ceilings.

SUPPORT PLATE WITH S/S CLAMP BAND (NON COMBUSTIBLE FLOOR)

Support plate for non-combustible floors, transferring chimney weight.

FIRE STOP PLATE (NON COMBUSTIBLE FLOOR)

Fire stop plate used exclusively for non-combustible floors.

Support Components (Wall Supports)

WALL BAND (60MM)

How to install wall bands for lateral support at 3-metre centres.

ADJUSTABLE BACK BRACKET 60-300MM

Installation of adjustable back brackets for lateral support.

STRUCTURAL WALL BAND

Use of structural wall bands for lateral stability at 4-metre centres.

STRUCTURAL WALL BAND EXTENSIONS

How to use extensions to adjust the distance of structural wall bands from the wall.

LOAD BEARING SUPPORTS

General information on load-bearing supports and their use with lateral supports.

BASE SUPPORT PLATE WITH DRAIN

Use of base support plate for floor support with integrated drain.

RETROFIT WALL SUPPORT

Installation of retrofit wall supports for existing structures.

ADJUSTABLE TOP PLATE

Use of adjustable top plates for internal or external support.

SIDE PLATES/CANTILEVER BRACKETS

How to secure side plates and cantilever brackets to the wall for support.

Cantilever Supports

Information on different types of cantilever supports and their specifications.

Cantilever Support Adjustment

Details on how to adjust cantilever supports for different chimney diameters.

Typical Installations

Ignis-Protect Installation Overview

Step-by-step guide for installing the Ignis-Protect system, covering all stages.

Safety and Health Precautions

Critical safety warnings, health instructions, and protective measures for installation.

Installation Tips

Useful tips and advice for ensuring a proper and efficient Ignis-Protect installation.

Protect Box

NEW HOUSING AIRTIGHTNESS REQUIREMENTS

How the Protect Box kit ensures airtightness where chimneys pass through barriers.

INSTALLATION

How to install the Schiedel airtight kits tailored for ICS50 chimneys.

SEALING TAPE

Properties and application of the special sealing tape used with airtight kits.

APPLICATION

How the tape attaches the EPDM seal to vapour/wind barriers on specific surfaces.

Support Components (Roof & Ceiling)

ROOF SUPPORT

How to install roof supports for chimney stability above roof trusses.

CEILING HANGER

How to use ceiling hangers to support horizontal chimney runs.

GUY WIRE BRACKET

Use of guy wire brackets to secure unsupported chimney sections above roof level.

TELESCOPIC ROOF STAYS

How telescopic roof stays provide extra support on chimneys above roof level.

WALL SLEEVE (90° & 135° VARIANTS)

How to install wall sleeves to protect buildings where chimneys pass through walls.

TWO PIECE TRIM COLLAR (90° & 135° VARIANTS)

How to fit trim collars where the chimney protrudes through walls.

ANGLED FLASHING

Use of angled flashing for pitched roofs, requiring sealing and storm collar.

FLAT FLASHING

Use of flat flashing for flat roofs, requiring sealing and storm collar.

STORM COLLAR

How to seal the storm collar to the flue above the flashing.

UNIFLASH

How to use Uniflash for watertight flashing on pitched roofs.

TERMINALS

How to secure terminals to the chimney system using a locking band.

System Design

OUTLET SITING

Recommendations for flue outlet positioning based on appliance type and standards.

FLUE ROUTING

Guidelines for routing the chimney, including vertical runs and offsets.

TERMINAL TYPES

Recommended terminal types for solid fuel and other appliances.

PROVISION FOR SWEEPING, CLEANING AND MAINTENANCE

How to ensure easy inspection, sweeping, and maintenance of the chimney.

OUTLET SITING FOR OIL APPLIANCES (<45KW)

Outlet siting clearances for oil appliances based on location.

OUTLET SITING FOR SOLID FUEL APPLIANCES (<50KW)

Outlet siting clearances for solid fuel appliances based on weather surface.

ROOM VENTILATION

Requirements for adequate air supply to the room containing the appliance.

PROVISION FOR CONDENSATE DISPOSAL

How to manage condensate from condensing appliances, including slope and drainage.

COMMERCIAL INSTALLATIONS

Information on Schiedel's design and sizing advice service for commercial projects.

Typical External Installations

Floor Mounted Installation with Base Drain Section

Diagram of a floor-mounted installation with a base drain section.

Wall Mounted Installation with pair of Cantilever Brackets and Structural Locking Bands

Diagram of a wall-mounted installation with cantilever brackets and locking bands.

Offset Installation (45°) with pair of Side Plates

Diagram of an offset installation using side plates.

Distance between Lateral Supports

Tables showing support spacing for different chimney diameters and support types.

Load Bearing Data

Maximum Load Bearing (metres of pipe)

Load bearing capacity in metres of pipe for different components and diameters.

Component Weights

Approximate Weights of Finished Goods (Kg)

Weights of components in kilograms for different diameters and lengths.

After Installation

TESTING AND COMMISSIONING PRIOR TO FIRST USE

Procedure for flue flow testing and commissioning before initial operation.

APPLIANCE OPERATION

Recommended operating procedures for appliances, including high fire conditions.

MULTI-FUEL APPLICATIONS

Guidance on using multi-fuel appliances and fuel mixing risks.

MAINTENANCE

Recommendations for chimney inspection, sweeping, and cleaning by competent persons.

FUEL STORAGE AND USAGE

Guidelines for proper storage and usage of solid fuels.

NOTICE PLATE FOR ICS PRODUCT

Requirements for marking and fixing the notice plate for ICS products.

Product Guarantee

Product Guarantee

Conditions for the ICS system's 10-year conditional guarantee.

Schiedel Installer Rewards

Schiedel Installer Rewards

How installers can earn points and redeem rewards for registering installations.

Useful Guides

THE SCHIEDEL INSTALLATION APP

Details on the mobile app for installation guides, videos, and FAQs.

YOUTUBE TV CHANNEL

Information on the YouTube channel for installation examples in 3D diagrams.

DOWNLOADS SPECIALIST CENTRE

Resources for architects and builders, including CAD files and typical installations.