SEL-2890 Instruction Manual Date Code 20210715
Settings and Commands
Settings
3.2
TUNNEL Serial tunnel mode N, Cmd,
Telnet, TCP, BTCP
N
TUNNEL_IP Tunneling remote IP
address (hidden if
TUNNEL=N or Cmd)
IP address
a
UDDELAY Unsolicited detection
delay
b
1–60 seconds 2
MTDELAY Message timeout delay
b
0.0–5.0 seconds 0.8
WEB HTTP type
b
SEL, User, Custom,
OFF
SEL
DHCP
g
Enable DHCP
b
Y, N N
DNS_IP Domain name server IP
address
b
IP address
a
192.168.0.1
DOMAIN Domain name of the
domain name server
b
Text name setting Empty
c
HOST_NAME Host name for the
SEL-2890
b
Text name setting Empty
c
EMAIL Enable email
b
Y, N N
Email Client Settings (available if EMAIL is set to Y and TUNNEL=N)
EMAIL_IP Email server address IP address
a
192.168.0.1
EMAIL_DOMAIN Email domain name Text name setting,
NA if not required
NA
TO Destination email address Text setting Empty
c
FROM From line text alias for
email
Text setting SEL2890
SUBJECT Email subject line Text setting Unsolicited
ROUTE Serial protocol routing
enable
Y, N N
Serial Routing Settings (available if ROUTE is set to Y and TUNNEL=N)
ROUTE_PORT1
d
Routing destination port 1 1026–65535,
0 disables
8001
ACCEPT1
d
Accept routing connection Y, N N
Table 3.1 SEL-2890 Settings Summary (Sheet 2 of 4)
Setting Name Description Range
Default
Value

Table of Contents