Intelligent Fire Alarm Network
User Guide
MMX
TM
LT-893SEC Rev 1
May 2017

Other manuals for Secutron MMX-2009-12NDS

Questions and Answers

  • J
    Jesus PhelpsAug 20, 2025
    Why does my Secutron Fire Alarm show 'Unconfigured CPU Trouble'?
    • N
      Nicole BlakeAug 20, 2025
      The 'Unconfigured CPU Trouble' message on Secutron Fire Alarms appears when annunciators or loop adders connected to the panel are either not programmed in the Configurator or are configured with an incorrect address.
  • N
    Nicole PorterAug 22, 2025
    What to do if my Secutron Fire Alarm displays 'I/O Adder Mismatch Trouble'?
    • P
      Penny ParkerAug 22, 2025
      The 'I/O Adder Mismatch Trouble' message on Secutron Fire Alarms shows when the hardwired adder modules are in the wrong order, the wrong quantity, or not connected. Ensure the number of physical hardwired adder modules matches the configuration and that they are properly connected.
  • J
    Julie ZimmermanAug 25, 2025
    Why am I getting a 'Display Mismatch Trouble' on my Secutron Fire Alarm?
    • M
      Marcus ParkerAug 25, 2025
      The 'Display Mismatch Trouble' message on Secutron Fire Alarms indicates that the number and order of display modules (RAX-1048/TZ, FDX-008, and IPS-2424) connected to the panel do not match the configuration. Verify that the display modules are connected correctly.
  • J
    Jamie MolinaAug 26, 2025
    What does 'Unconfigured Device Trouble' mean on my Secutron Fire Alarm?
    • D
      daryl55Aug 26, 2025
      The 'Unconfigured Device Trouble' message on Secutron Fire Alarms appears when an analog device is physically installed but is not included in the configuration program.
  • D
    David SmallAug 27, 2025
    How to fix 'Printer Data Loss Trouble' on a Secutron Fire Alarm?
    • E
      Eddie ClarkeAug 28, 2025
      The 'Printer Data Loss Trouble' message on Secutron Fire Alarms indicates that a printer is configured but not physically connected to the panel when a message is sent to it. Clear this trouble by pressing the System Reset button.
  • R
    rodriguezgeorgeAug 30, 2025
    What causes 'Slave (RAXN-LCDs) Configuration Version Mismatch Trouble' on Secutron Fire Alarms?
    • M
      Matthew CarterAug 30, 2025
      The 'Slave (RAXN-LCDs) Configuration Version Mismatch Trouble' message on Secutron Fire Alarms means that the firmware versions on all the CPUs are not compatible.
  • D
    Dawn AguirreSep 1, 2025
    Why does my Secutron Fire Alarm show 'Slave (RAXN-LCDs) Configuration Address Mismatch Trouble'?
    • R
      Rebecca MccannSep 1, 2025
      The 'Slave (RAXN-LCDs) Configuration Address Mismatch Trouble' message on Secutron Fire Alarms appears when the addresses of the configured slaves do not match.
  • P
    philipjohnsonSep 2, 2025
    What does 'Slave Configuration Type Mismatch' mean for Secutron Fire Alarms?
    • J
      Joanne OliverSep 2, 2025
      The 'Slave Configuration Type Mismatch' message on Secutron Fire Alarms indicates that the physical loop adder does not match the loop adder type specified in the configuration program. For example, this will appear if the physical adder module is an ALC-396, but the configuration program specifies an ALC-H16.
  • J
    Jimmy ThorntonSep 5, 2025
    Why is my Secutron Fire Alarm displaying 'Wrong Device Type'?
    • V
      veronica36Sep 5, 2025
      The 'Wrong Device Type' message on Secutron Fire Alarms shows if the type of analog device does not match the type listed in the configuration program. For example, this message appears if an ionization sensor is connected at address 013, but the configuration program lists address 013 as a photoelectric sensor (or vice versa).
  • K
    Kathy GuzmanSep 7, 2025
    What causes the 'Multiple Unconfigured Device Trouble' on Secutron Fire Alarms?
    • J
      Jimmy ThompsonSep 7, 2025
      The 'Multiple Unconfigured Device Trouble' message on Secutron Fire Alarms indicates that there are two identical (duplicate) devices at the same address on the same loop.