30
Editing MHI Databases
2.8.18 Dialer Settings
The Dialer Settings dialog (see Figure 13) allows for the programming of various
communications options.
Figure 13 Dialer Settings
The 1
st
, 2
nd
and 3
rd
Telephone Numbers can be up to 32 digits. Special digits may be used to
perform the following functions:
HEX (B)-simulates the [*] key
HEX (C)-simulates the [#] key
HEX (D)-forces the panel to search for dial tone; must be first digit of telephone number
HEX (E)-forces the panel to pause for 2 seconds
HEX (F)-end of telephone number marker
Note: Networking is limited to two nodes for ULC applications.
Key Action
General Alarm See General Alarm on page 29 for information about this key.
Automatic
Alarm Signal
Cancel
Configure one of the four remaining keys as Automatic Alarm Signal Cancel and
label it as follows:
Note: This key is optional.
See Automatic Alarm Signal Cancel (Second Stage Inhibit) on page 28 for
information about this key.
i
AUTO ALM SIG CANCEL
TMR CANCELLED
(yellow)
TMR ACTIVE
(green)