1
Operation and Programming Concepts
1.0 Operation and Programming
Concepts
1.1 Introduction
This chapter provides an overview of the MR-2100/2200’s (hereafter called the MR-2200)
features and supported devices.
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the
requirements in CAN/ULCS527, Standard for Control Units for Fire Alarm Systems, certain programming
features or options must be limited to specific values or not used at all as indicated below.
Program feature or
option
Permitted in CAN/
ULCS527? (Y/N)
Possible settings\methods
Settings permitted in
CAN/ULCS527
Bell System Y
Alert, Evac, Alert/Evac,
Staged
Alert, Evac
Bell Cutoff Y 0 or 5 to 30 minutes All
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the
requirements in UL864, Standard for Control Units for Fire Alarm Systems, certain programming features or
options must be limited to specific values or not used at all as indicated below.
Program feature or
option
Permitted in UL864?
(Y/N)
Possible settings\methods
Settings permitted in
UL864
AC Fail Y 0 to 30 hours 1, 2 or 3 hours
Bell Cutoff N 0 or 5 to 30 minutes 0