48
LCD Programming
Test: Select devices to be tested. Test Mode must be active for this selection to be
available. All devices selected for testing are automatically deselected when Test Mode
is turned off. The Test Menu has the following options:
-- ON: Select devices for testing. Enter the circuit and device number, or enter the
circuit number only to select all devices on the circuit. Press <Enter> to accept the
device and to enter the next one. Pressing <Clear> removes any numbers
entered. Pressing either <Enter> or <Clear> with no numbers displayed ends the
input mode.
-- OFF: Select devices under test to be returned to normal operation. Each device
under test is listed in order. Select next to keep the device under test or select OFF
to remove the test mode. After the last device, display returns to the Test menu.
Press <Clear> to return to the Test Menu. This option is not available if there are
no devices selected for testing.
-- ALL OFF: Remove all devices being tested, if any, from the test mode. The number
of devices being tested is displayed next to this option.
Control Modules: This function can be set to Privilege Level 1 or 2. Allow for the
manual operation of the control modules included in the database. There are three
states available: Automatic (controlled by device inputs), Manual On, and Manual Off.
This mode is retained if the panel is re-booted. Manually controlled modules are
annunciated by a common trouble condition. The menu has the following options:
-- SELECT: Change the Auto/On/Off state of control modules. The first screen asks
for a circuit and device number. Enter the circuit and device or press <Enter>
without entering any number to view the first control module in the database. Each
control module is displayed in turn, showing the current state and allowing for it to
be changed or the next control module to be displayed. Press <Clear> to stop
viewing the control module list.
-- ALL AUTO: Change any control modules that are forced on or off back to automatic
mode.
3.3.6 Archive
This function is restricted to Privilege Level 2. View and change the settings for the recording
of optional entries into the history. The following items can be included or not included in the
history:
Test: View or change whether Test signals should be recorded in the history. The current
setting is shown in the upper right corner. Test signals are marked as such.
Non-Reporting: View or change whether non-reporting signals are recorded in the
history or not. Non-reporting signals are recorded by default.
Network: View or change the type of archive events that the panel will record in the
archive. This is only available on the network master panel. The options are:
-- LOCAL: Record only panel events in the archive.
-- GLOBAL: Record all events in the archive.
3.3.7 Relays
This function can be set to Privilege Level 1 or 2. If Privilege Level 1 is set and Level 2 is
required, access to the menu is denied. This function allows for the manual operation of the
relays. There are three possible states: Automatic (state determined by inputs), Forced On, or
Forced Off. This mode is retained if the panel is re-booted.