SELCO A/S M2500 Installation Manual
Revision: 23-04-2012 Page 10
4.2.4 Override (terminal 10)
The Override input is considered active
when connected to COM, inactive
when open.
When activated all shutdowns that are
marked override will be disabled,
meaning the engine will continue
running despite of a shutdown. If the
override is deactivated while a
shutdown is present, shutdown will be
executed immediately.
4.2.5 Crank Disconnect (terminal 11)
The Cranck Disconnect input is
considered active when connected
to COM, inactive when open.
This input is only used in case
there is no pick-up for speed
detection. The input is a contact
from a tacho-relay that signals
that the speed of the engine is
above ignition speed. When
receiving the Crank Disconnect
signal the M2500 will deactivate
the crank output after a start
attempt. If the M2500 looses this
signal without a stop procedure, the ALARM LED will be lit and a Tacho Fail Alarm will be
displayed.
4.2.6 Reset (terminal 12)
This Reset is considered active when
connected to COM, inactive when open.
When activated, this input will reset the siren
and the alarm/ shutdown.