EasyManua.ls Logo

Selco M2500 - Siren Relay

Default Icon
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SELCO A/S M2500 Installation Manual
Revision: 23-04-2012 Page 26
5.6 Siren Relay
Nr.
Description
Type
Rating
68
ND
Relay contact in de-energized position
1A
69
REF 5
Reference contact of alarm relay
1A
70
NE
Relay contact in energized position
1A
The siren relay is typically used for connection of a siren. It is normally energized.
It will de-energize with any new alarm or shut-down. After pressing RESET the alarm relay will
energize again.
5.6.1 Connection of the Siren Relay
In below example the siren will activate with any new incoming alarm or shutdown.