User Manual ESY-1 / rev. 9 15.01.2008 www.selproweb.com
5
i
4. TECHNICAL CHARACTERISTICS ESY-1
POWER SUPPLY
Voltage
AC
single phase – (on request
AC
AC)
Frequency
standard
only factory calibration)
Overvoltage Protection for installation Category
(
)
OPERATING
PRINCIPLE
Electronic analog regulators of single-phase AC voltage, which use the phase-cutting principle (Triac) in order to vary the
output active voltage applied to a resistive or inductive load.
CURRENT
Rated
ESY 08
up to
environment; if over, decrease 0,4
ESY 12
up to
environment; if over, decrease 0,6
ESY 16
up to
environment; if over, decrease 0,8
ESY 20
up to
environment; if over, decrease 1,0
Starting current
(for loads upstream of the regulator)
ESY 08 16A
ESY 12 24A
ESY 16 32A
ESY 20 40A
Overload
200% of the rated current (max. 10” every 3’)
POWER
Control Circuit
3VA
Thermally dissipated
1,3 W per supplied Ampere
OPERATING
CHARACTERISTICS
Master (Controller Mode)
(inputs IN1,IN2,IN3)
The output voltage varies in order to maintain the value measured by the
transducer within the proportional band (Pb = factory calibration)
Slave (Power Unit Mode)
(Input IN4)
The output voltage varies according to the 0-10 Vdc control signal applied to the
input IN4, according to the current configuration.
CONTROL
SIGNALS
AND
CONTACTS
ALL-in-ONE
standard
Config. 0M
Master (Controller)
IN 1
IN 2
IN 3
4-20 mA for 100 ohm (R)
4-20 mA for 100 ohm (R)
NTC 10kohm @ 25°C
Slave (Power Unit)
IN 4
0-10Vdc for 10 kohm
On request
Config. 0X
Master (Controller)
IN 1
IN 2
IN 3
4-20 mA for 100 ohm (R) ,
NTC 10 kohm @ 25°C
NTC 10 kohm @ 25°C
Slave (Power Unit)
IN 4
0-10Vdc for 10 kohm
Config. 0V
Master (Controller)
IN 1
IN 2
IN 3
0-5 Vdc
0-5 Vdc
NTC 10 kohm @ 25°C
Slave (Power Unit)
IN 4
0-10Vdc for 10 kohm
Config. 0B
Master (Contoller)
IN 1
IN 2
IN 3
4-20 mA for 100 ohm (R)
0-5 Vdc
NTC 10 kohm @ 25°C
Slave (Power Unit)
IN 4
0-10Vdc for 10 kohm
Contact for Set-Point switching SP2: selection of Set Point 1 or Set Point 2 (option Double Set-Point )
SLAVE
ONE
Standard
Config. SV
Slave (Power Unit)
IN 1
0-10Vdc for 10 kohm
Config. SP
Slave (Power Unit)
IN 1
PWM (PPM-Triac) control voltage 5V÷30V
OPERATING
PARAMETERS
Set-Point Regulation Easy adjustment with couple of 13-position rotary switches
Input type
4-20 mA
0 - 5 Vdc NTC 10K @ 25°C
Main Set Point (SP)
8÷18 mA 0,5 - 4,5 Vdc 10÷60 °C
Step Set Point adjustment (SPadj)
0,1 mA 0,04 Vdc 0,5 °C
Proportional Band (default)
2,5 mA 0,65 Vdc 7°C
Minimum/Cut-Off limit Adjustable from 0% to 70% of the output voltage
Maximum limit Adjustable from 100% to 0% of the output voltage
Acceleration time (default) 5”
Operating mode
(
VAC output increases as the input value increases)
REVERSE (REV) VAC output decreases as the input value increases)
AC voltage at Set Point
Selection of
value – maximum fan speed
Selection of MIN Vac value – minimum fan speed
Lower VAC limit
Selection of
limit
(C-Off) o
Selection of MAX Vac Limit (MIN)
Slave Units AUX. control
Selection for
signal (three / single phase supply)
Selection for logic PWM signal (same as the remote unit supply)
LED
SIGNALS
DL1
Power Supply O.K.
-
Signal value is lower than Set-Point value
± 30% of the Proportional Band (Pb)
+
Signal value is higher than Set-Point value
1
Set-Point 1 selection
Available optional card with
Double Set-Point function
2
Set-Point 2 selection