2: Meter Overview and Specifications
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
2.1.5: Utility Peak Demand
The Shark® 100/50 meter provides user-configured Block (Fixed) Window or Rolling
Window Demand. This feature lets you set up a customized Demand profile. Block
Window Demand is demand over a user-configured demand period (usually 5, 15 or
30 minutes). Rolling Window Demand is a fixed window demand that moves for a
user-specified subinterval period. For example, a 15-minute demand using 3 subinter-
vals and providing a new Demand reading every 5 minutes, based on the last 15 min-
utes.
Utility Demand features can be used to calculate kW, kVAR, kVA and PF readings. All
other parameters offer Max and Min capability over the user-selectable averaging
period. Voltage provides an instantaneous Max and Min reading which displays the
highest surge and lowest sag seen by the meter.
2.2: Specifications
Power Supply
Range: D2 Option: Universal, (90 to 265)
VAC @50/60Hz or (100 to 370)VDC
D Option: (18-60) VDC (The
Shark® 50 meter has the D2 Power
Supply, only)
Power Consumption: 5 VA, 3.5W
Voltage Inputs (Measurement Category III)
Range: Universal, Auto-ranging up to
416VAC L-N, 721VAC L-L
Supported hookups: 3 Element Wye, 2.5 Element Wye,
2 Element Delta, 4 Wire Delta
Input Impedance: 1M Ohm/Phase
Burden: 0.0144VA/Phase at 120 Volts
Pickup Voltage: 10Vac
Connection: Screw terminal (Diagram 4.4)