Notice
Please ensure that this instruction manual is given to the final user of the instrument.
Preface
This instruction manual is meant for those who will be involved in the wiring, installation, operation and routine
maintenance of the SR90 series (SR91, SR92, SR93 and SR94) and describes matters to be attended to in handling
the SR90 series, how to install it, its wiring, its functions and operating procedures.
Keep this manual at the work site while handling the instrument and follow the guidance provided herein.
SR90F-1ME
Aug. 2019
SR90 Series
(SR91, SR92, SR93, SR94)
Digital Controller
Instruction Manual
Please check that the delivered product is the correct item or specification you ordered.
Please do not begin operating this product before you read this instruction manual
thoroughly and understand its contents.

Table of Contents

Questions and Answers

  • J
    Juan MoralesAug 20, 2025
    What to do if the Shimaden SR94 Controller displays an incorrect PV value?
    • S
      stevengrantAug 20, 2025
      If the displayed PV value seems incorrect, verify that the set measuring range code is correct for the input signal. Also, check the wiring to the input terminals of the sensor and correct if necessary.
  • C
    chelseatylerAug 22, 2025
    What to do if the Shimaden SR94 Controller front panel display goes out and it stops operating?
    • M
      Marvin MorrisAug 22, 2025
      If the display on the front panel goes out and the instrument does not operate, inspect the power source and wiring connections, checking the wiring. Additionally, examine the product for deterioration and repair or replace it as needed.
  • C
    Charles HintonAug 25, 2025
    Why is my Shimaden Controller key unable to be operated?
    • T
      Tara UnderwoodAug 25, 2025
      If a key is unable to be operated, it may be because the keylock is active, so release the keylock. Another reason could be deterioration of the product, in which case you should examine, repair, or replace the product. If the communication function is added, check if the communication mode (Com) has been set, and if so, change the communication setting to the local mode (Loc).
  • D
    Diane TravisAug 26, 2025
    What to do if Shimaden SR94 indicates higher limit side scaleover?
    • B
      Benjamin HillAug 27, 2025
      If the controller indicates a higher limit side scaleover, check the thermocouple input wiring for breaks and replace if necessary. Also, check R.T.D. input A wiring for breaks and replace the R.T.D. if needed. For voltage or current input, verify the transmitting unit of measured values and ensure the set code of the measuring range is correct for the input signal; it may be that the input measured value exceeded higher limit of measuring range by 10%.
  • A
    Andrew Murray Jr.Aug 28, 2025
    How to fix too fast ON-OFF action of Shimaden SR94 Controller control output?
    • K
      keyryanAug 28, 2025
      If the ON-OFF action of the control output is too fast, increase the hysteresis value of the ON-OFF action.
  • W
    Wanda HudsonAug 30, 2025
    What does it mean if the Shimaden SR94 shows a lower limit side scaleover?
    • V
      Vincent SullivanAug 30, 2025
      If the controller shows a lower limit side scaleover, check the wiring for reverse polarity or breaks in the measured value input; it may be that the input measured value fell from lower limit of measuring range by 10%.
  • E
    Erica CarrollSep 1, 2025
    What to do if Shimaden Controller displays higher limit side scaleover of cold junction (CJ)?
    • M
      michellelittleSep 1, 2025
      If the controller displays a higher limit side scaleover of the cold junction (CJ), reduce the ambient temperature to the level provided in the environment conditions for the product, if the ambient temperature of the product has exceeded 80°C. In case ambient temperature has not exceeded 80°C, examine the product.
  • A
    Ashley BennettSep 3, 2025
    What to do if Shimaden SR94 displays higher limit side scaleover of cold junction (CJ) of thermocouple input?
    • J
      jrodriguezSep 3, 2025
      If the Shimaden Controller displays a higher limit side scaleover of the cold junction (CJ) of thermocouple input, raise the ambient temperature to the level provided in the environment conditions for the product if the ambient temperature of the product has fallen to -20°C or lower. In case ambient temperature has not fallen to í20°C or lower, examine the product.
  • B
    Brittany MitchellSep 5, 2025
    What to do if there is a break of R.T.D. input wiring in Shimaden SR94?
    • R
      robert61Sep 5, 2025
      Check R.T.D. input terminals A, B and B for breaks. If wiring has no problem, replace R.T.D.
  • X
    xbeckerSep 7, 2025
    What does it mean if Shimaden SR94 input value from heater current detector has exceeded 55.0A?
    • H
      hallstephanieSep 7, 2025
      If the input value from the heater current detector has exceeded 55.0A, it indicates excess current. Reduce the current. Also, examine the product.

Summary

Safety Rules

Installation and Wiring

Installation Site (Environmental Conditions)

Specifies suitable locations and environmental conditions for instrument installation.

Mounting

Instructions for physically installing the controller onto a panel.

Wiring

Detailed instructions and precautions for connecting the instrument's terminals.

Terminal Layout

Illustrates the physical terminal connections for SR91, SR92, and SR93/SR94 models.

Terminal Arrangement Table

Lists terminal numbers and their corresponding functions for different models.

Before Starting Operation

Outlines the initial checks and settings required before operating the controller.

Front Panel Overview

Screens and Settings

Procedure of Setting in Screen Group 0

Details the step-by-step process for configuring the controller's parameters.

Screen Group and Setting Explanation

Table of Measuring Range Codes

Explanation of Functions

Events

Explains different types of alarms like deviation and absolute value alarms.

PID Control Parameters

Explains Proportional (P), Integral (I), and Derivative (D) control parameters.

Maintenance and Troubleshooting

Cause of Trouble and Troubleshooting

Lists common problems, their causes, and remedies.

Error Codes, Causes, and Remedies

Details specific error codes, their causes, and recommended solutions.

Specifications

Shimaden SR94 Specifications

General IconGeneral
Control MethodPID control
Input TypeThermocouple, RTD, DC Voltage, DC Current
Power Supply100 to 240 VAC, 50/60 Hz
Output TypeRelay
DisplayDigital LED display
Dimensions96 x 96 x 100 mm
Operating Temperature0 to 50°C
Accuracy±0.3% of full scale